11
If T2﹥TE7, this unit turns into the protection of compressor off , and quits this protection when T2≤TE9.
If T2﹥TE8,it turns into the protection of fan motor off , and quits this protection when T2≤TE9.
If T2﹥TE15, fan motor operates at low speed by force, then quits the operation and determines the high
or low speed by T4.
6.4.5. At the fan only mode, the fan always keeps on working, and the compressor/fan motor/heater stop
working.
6.5 Operation of compressor
6.5.1. The compressor operates at cooling mode as below:
(T1-Ts)
℉
+0
-4
Compressor on
Operation conditon
Compressor off
T1≥Ts compressor on
T1≤Ts-4℉ compressor off
6.5.2. The compressor operates at heating mode:
(There are two ways of heating mode: Heat pump and cooling/Electric heater and cooling)
The electrical heater or compressor will be activated by sensing the difference between setting
temperature and the actual ambient room temperature.
TE7
TE8
TE15
TE9
Compressor
Fan motor
Fan motor
(low speed)
Compressor on
Fan motor on
(High/low speed is
determined by T4)
Compressor
Fan motor
Compressor on
Fan motor on
(High/low speed is
determined by T4)