EVAX 25 / 50 / 100
SIG
CKT
FACP EOLR
3
3
4
5
6
4
5
6
R1
R2
R1
(See NOTE 1) End of line
resistor for FACP Signal Circuit.
NOTE 1: If the Fire Alarm Signal Circuit requires a
4.7K end-of-line resistor, then R1 must be a 4.7K.
Normally, this resistor is connected to the Signal
Circuit through a closed Trouble contact. When the
EVAX 25/50/100 goes into Trouble, the contact
opens, producing an "Open" on that Signal Circuit,
notifying the FACP.
EVAX 25 / EVAX 50 / EVAX 100
END OF LINE RESISTORS
SET EOLR
R2
(See NOTE 2) Sets the
value of the end of line
resistor for the Speaker
Circuit.
R3
(See NOTE 2)
End of line resistor for Speaker Circuit.
NOTE 2: R2 and R3 must match each other. R2
"Sets" what the value of R3 needs to be. R2 tells the
EVAX 25/50/100 what to expect on the end of the
Speaker Circuit. If a Speaker EOLR (R3) already
exists, simply match that value for R2.
SPEAKER EOLR
R3
NOTE: These connections
are internal. Do NOT make
these connections.
*
NAC Circuit MUST be Steady to play Voice message
Field wiring connections:
#6-32 wire clamp screw 14-18 AWG
#8-32 wire clamp screw 12-18 AWG
Horizontal wire entry terminal 18-26 AWG
Wire gauge determined by circuit load
HARRINGTON
FIRE ALARM
SIGNAL INC.