Fire alarm, Harrington, Switch settings – Harrington Signal HAVE 100 User Manual
Page 7: Trouble codes

EVAX 25 / 50 / 100
SWITCH SETTINGS
ON = 1 (DOWN)
OFF = 0 (UP)
Switch Network Detail
1
8
SN1
Default = 0/1/0/1/0/1/0/1
SW 1/2/3
Sets the initial delay before the message starts
to play. Tone sounds during delays.
8 Settings:
0/0/0 No delay
1/0/0 4 second delay
0/1/0 8 second delay
1/1/0 12 second delay
0/0/1 16 second delay
1/0/1 20 second delay
0/1/1 24 second delay
1/1/1 28 second delay
Sets the delay between repeats of the message.
4 Settings:
0/0 4 second delay
0/1 8 second delay
1/0 12 second delay
1/1 16 second delay
Sets the message play.
2 Settings:
0 Message off
1 Message on
Sets the number of times the message plays.
4 Settings:
0/0 1 play
0/1 3 plays
1/0 2 plays
SW 4/5
SW 6
SW 7/8
EVAX 25 / 50 / 100
TROUBLE CODES
SN2
Default = 0/0/0/0/0/0/1/1
SW 1/2/3
Sets the evac tone.
8 Settings:
0/0/0 Temporal slow whoop
1/0/0 Hi Lo
0/1/0 Horn
1/1/0 Bell
0/0/1 Empty
1/0/1 Chime
0/1/1 None
1/1/1 1kHz Sine
Sets the diagnostics mode.
2 Settings:
0 Diagnostics off
1 Diagnostics on
NA
AC power failure report delay.
2 Settings:
0 No delay
1 6 hour delay
Batteries.
2 Settings:
0 Batteries are not connected
1 Batteries are connected
Microphone.
2 Settings:
0 Microphone is not connected
SW 4
SW 5
SW 6
SW 7
SW 8
When a unit goes into a Trouble Condition, the Yellow LED wil remain on until the trouble is cleared.
The Green LED will flash a Code to indicate the type of Trouble Condition. There will be a pause between
repeats of the code. W
The number of flashes and associated Trouble Condition are listed below.
1
Power Failure
2
Open Speaker Circuit
4
Shorted Speaker Circuit
hen multiple Trouble Conditions occur at the same time, the codes will add
together.
8
Amplifier Trouble
16
Microphone Trouble
32
Battery Trouble
Code
Trouble
Code
Trouble
S1
SN2
SN1
* 6 flashes typically indicates “External Trouble”, such as an EVX-RM. If LED 4 is on, the 6 flash indicates a ground fault.
If both a ground fault condition and an external trouble occur simultaneously, the fault codes will
combine for 12 flash.
not