Terminal designations, Fire alarm, Harrington – Harrington Signal HAVE 100 User Manual
Page 2: Factory default switch / jumper settings

EVAX 25 / EVAX 50 / EVAX 100
TERMINAL DESIGNATIONS
TB1:
1 4
1 4
TER 1 & 2
TER 3 & 4
TER 5 & 6
- Power Input 24-32V AC/DC (NOTE , )
- FACP Signal Circuit Input - 10mA max. (Alarm Polarity shown) (NOTE
, )
- 25/70 VRMS Speaker Loop Style Y/Z (Class “A”/”B” start) (NOTE ,
2
TB3:
1 4
1 3 5
TER 1 & 2
TER 3 & 4
TER 5 & 6
TER 7
(NOTE , )
FACP Signal/Supervisory
Circuit EOLR
Matching EOLR for speaker
supervisory circuit
(NOTE , , )
General purpose output (pulls
to circuit neg on fault
condition
32V - 0.2A max). Not for Fire
Protective Signaling use.
Optional FACP Supervisory
Circuit (See installation
instructions page 5 diagram 2
for details (32V - 0.4A max.)).
Factory set for none - J1
(installed)
NOTES:
- Intended for connection to
Listed Class 2 / Class 3 (Power
Limited) sources only.
- Power Limited
- Non-Supervised
- Supervised
- Terminating equipment must
be installed in same room as
1
2
3
4
5
1 = OFF 8 sec. initial delay
2 = ON
3 = OFF
4 = ON 8 sec. repeat delay
5 = OFF
6 = ON Message On
7 = OFF 3 Repeats
8 = ON
SN1
FACTORY DEFAULT SWITCH / JUMPER SETTINGS:
1 - 2 = SHORT
J1 A/B
1 + 2 SHORT = Ground Fault Enable
J5
25 VRMS 2-3 = SHORT
70 VRMS 1-2 = SHORT
J2
To change output voltage
move shorting block.
SN2
1 = OFF Temporal Whoop Signal
2 = OFF
3 = OFF
4 = Fault Code Lock
5 = X Do not use
6 = AC Fault Delay
7 = ON Battery connected
8 = ON Mic connected
(default up (off))
(default up (off))
1
8
ON
OFF
Switch Network Detail
TB2:
1 3
1 3 5
1 3 5
1 3 5
1 3
1 3
2 3 5
2 3
2 3
5
- Circuit Neg
(NOTE , )
Aux Audio Input
(0.5V nominal)
(1VRMS - 1mA max.)
(NOTE , , )
PreAmp In/Out
(600 Ohm 0dBm)
(NOTE , , )
Master - Programmable
+24VDC Active
Slave - +24VDC Input
(NOTE , , )
Signal Active
Master - Out / Slave - In
(NOTE , )
Aux Audio Enable
(+24V)(32V - 5mA max.)
(NOTE , )
Aux Signal Activate
(+24V) (32V - 5mA max.)
(NOTE , , )
Alarm Voltage +24V
when unit is in alarm
condition (0.1A)
(NOTE , )
Int V+ (+24V)
disconnected in alarm
condition (0.1A)
(NOTE , )
V+ (+24V 0.1A)
(NOTE )
Mic PTT (+24V 0.1A)
TER 1
TER 2
TER 3
TER 4
TER 5
TER 6
TER 7
TER 8
TER 9
TER 10
TER 11
1
2
TB1
1
2
3
4
5
6
7
8
TB3
1
2
3
4
5
6
7
8
MSG
GAIN
MIC
GAIN
FAULT
NORMAL
ALARM
YEL
YEL
GROUND
FAULT
GRN
RED
TB2
1
2
3
4
5
6
7
8
9
10
11
P2
U6
S1
SN2
SN1
1
2
3
J2
J5
J1
1
2
70V 25V
1
2
3
4
Field wiring connections:
#6-32 wire clamp screw 14-18 AWG
#8-32 wire clamp screw 12-18 AWG
Horizontal wire entry terminal 18-26 AWG
Wire gauge determined by circuit load