beautypg.com

Danger, Warning – Burnham Series 2B User Manual

Page 10

background image

10

DANGER

Inspect existing chimney before installing boiler.

Failure to clean or replace perforated pipe or tile

lining will cause severe injury or death.

A. vent installation shall be in accordance with local

building codes; or the local authority having

jurisdiction; or the National Fuel Gas Code, ANSI

Z223.1/NFPA 54; or the Standard for Chimneys,

Fireplaces, vents, and Solid Fuel Burning

Appliances, ANSI/NFPA 211. Both of the

aforementioned standards, ANSI Z223.1 and ANSI/

NFPA 211, specify Type B and Type L double wall

metal vents and fire clay tile lined masonry

chimneys as suitable chimney constructions for

Category I, draft hood equipped appliances, such as

this Series 2™ boiler. Both standards prohibit the

use of unlined masonry construction as a chimney,

with the exception in ANSI Z223.1/NFPA 54 that

"Where permitted by the authority having

jurisdiction, existing chimneys shall be permitted to

have their use continued when an appliance is

replaced by an appliance of similar type, input

rating, and efficiency." ANSI/NFPA 211 prohibits

the use of single wall metal vent as a chimney, while

ANSI Z223.1 allows it under very restrictive

conditions. In Canada refer to the Natural Gas and

LP Installation Code, CAN/CSA-B149.1.

B. Do not connect into same leg of chimney serving an

open fireplace.

C. Inspect chimney for obstructions or restrictions and

remove. Clean chimney if necessary.

D. vent pipe to chimney must not be smaller than outlet

on draft hood or damper. Although single wall vent

pipe may be used, Type B is recommended. The

venting system must be arranged so that only the

boiler is served by the damper device. Installation

per paragraph 12 complies with this provision.

E. Where two or more appliances vent into a common

vent, the area of the common vent should at least

equal the area of the largest vent plus 50% of the

area in the additional vents. Do not connect the vent

of this appliance into any portion of mechanical

draft system operating under positive pressure.

F. vent pipe should have the greatest possible initial

rise above the draft hood consistent with the head

room available and the required clearance from

adjacent combustible building structure. vent Pipe

should be installed above the bottom of chimney to

prevent blockage.

G. vent pipe should slope upward from draft hood to

chimney not less than one inch in four feet. Doivent

présenter des tronçons horizontaux dont la pente

montante est d’au moins ¼ po par pied (21 mm/m)

entre la chaudière et l’évent. No portion of vent

pipe should run downward or have dips or sags.

vent pipe must be securely supported. Les sections

horizontales doivent être supportées pour prévenir le

fléchissement.

h. vent pipe must be inserted into but not beyond

inside wall of chimney liner. Seal tight between vent

pipe and chimney.

I. Do not install non-listed (AGA, CGA, CSA, ETL or

UL) vent damper or other obstruction in vent pipe.

WARNING

14.

IF AN ExISTING BOILER IS REMOvED -

When an existing boiler is removed from a common

venting system, the common venting system is likely to

be too large for proper venting of the appliances

remaining to it.
At the time of removal of an existing boiler, the

following steps shall be followed with each

appliance remaining connected to the common

venting system placed in operation, while the other

appliances remaining connected to the common

venting system are not in operation:

A. Seal any unused openings in the common venting

system.

B. Visually inspect the venting system for proper size

and horizontal pitch and determine there is no

blockage or restriction, leakage, corrosion, and other

deficiencies which could cause an unsafe condition.

C. Insofar as is practical, close all building doors and

windows and all doors between the space in which

the appliances remaining connected to the common

venting system are located and other spaces of the

building. Turn on clothes dryers and any appliance

not connected to the common venting system. Turn

on any exhaust fans, such as range-hoods and

bathroom exhausts, so they will operate at maximum

Figure : Typical Vent Installation