Dimensions - weight, Feed water guidelines – Watts PWS30-2 User Manual
Page 2

Dimensions - Weight
Model No.
diMeNsioNs
WeiGHTs
A B C D E F G
in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs kgs
PWS30151H11 79
7
/
16
2017 79
7
/
16
2017 95
1
/
4
2419 24
1
/
2
622 24
1
/
2
622 30 762 50 1270 1070 486
PWS30151I11 81
7
/
16
2068 81
7
/
16
2068 96
3
/
4
2457 30
1
/
8
765 30
1
/
8
765 39 991 48 1219 1600 727
PWS30151J11 87
1
/
4
2216 87
1
/
4
2216 101 2565 36
1
/
8
917 36
1
/
8
917 39 991 60 1524 2015 916
PWS30151K11 95
1
/
4
2419 95
1
/
4
2419 108 2743 44 1118 44 1118 42 1067 60 1524
3245 1475
PWS30151L11 99
5
/
8
2530 99
5
/
8
2530 112
3
/
8
2854 50
3
/
8
1280 50
3
/
8
1280 50 1270 60 1524
4295 941
PWS30151H21 79
7
/
16
2017 79
7
/
16
2017 95
1
/
4
2419 24
1
/
2
622 85 2159 30 762 50 1270
2070 941
PWS30151I21 81
7
/
16
2068 81
7
/
16
2068 96
3
/
4
2457 30
1
/
8
765 100 2540 39 991 48 1219 3000 1364
PWS30151J21 87
1
/
4
2216 87
1
/
4
2216 101 2565 36
1
/
8
917 111 2819 39 991 60 1524 4015 1325
PWS30151K21 95
1
/
4
2419 95
1
/
4
2419 108 2743 44 1118 126 3200 42 1067 60 1524
6245 2839
PWS30151L21 99
5
/
8
2530 99
5
/
8
2530 112
3
/
8
2854 50
3
/
8
1280 150 3810 50 1270 60 1524
8295
3770
Feed Water Guidelines
pH . . . . . . . . . . . . . . . . . . . . . . . 6 to 10
Hardness (maximum) . . . . . . . . . Depends on customers acceptable
hardness leakage level.
Water Pressure . . . . . . . . . . . . . 25psi to 125psi (171 kPa to 8.5 bar)
Temperature . . . . . . . . . . . . . . . 34 - 110°F (1 - 43°C)
Free Chlorine (maximum) . . . . . . 1mg/L
Iron (maximum) . . . . . . . . . . . . . 1mg/L
Oil and H2S . . . . . . . . . . . . . . . . None Allowed
Turbidity
Less than 5.0 NTU
For all other guideline information please contact your Watts rep-
resentative.
FRONT
SIDE
A
B
G
F
C
E
D
e
C
F
G
B
d
A
FRoNT
side
FRONT
SIDE
A
B
G
F
D
E
C
e
C
F
G
B
d
A
FRoNT
side
PWs30-2 series
PWs30 series
Note:
Do not use with water that is microbiologically unsafe or
of unknown quality without adequate disinfection before or after
the system.