Specifications

A OneFlow

®

scale prevention system shall be installed on the

cold water service line to condition the tap water just prior to

the service line feeding the equipment it is designed to protect.

The system will be sized for maximum or peak flow rate based

on the specification of said equipment. A OneFlow

®

system may

also be installed to protect multiple pieces of equipment from

the ill-effects of hard water scale provided the aggregate peak

flow rate for each piece of equipment it is protecting has been

considered. The system shall be plumbed with a bypass valve to

allow isolation of filter housing to allow the bypass of untreated

water in the event that service or cartridge replacement be nec-

essary. The installation area should be suitable in size for the

housing to be serviced without encumbrance and the system

should be installed per the Installation, Operation & Maintenance

manual as provided with each system.
The OneFlow

®

system must not require additional waste water

to backwash, flush, or regenerate once put into service. The

system shall not require any chemical additives and shall not

require electricity for operation.

Note: Copper lines need to be passivized for a minimum of 4

weeks before placing unit into service. Not for use on closed

loop systems.

Water Chemistry & Limitations

pH

6.5 to 8.5

Hardness (maximum)

75 grains (1300 ppm CaCO3)

Temperature

41°F to 100°F (5° to 38°C)

Chlorine

< 3 ppm

Iron (maximum)

0.3 mg/l

Manganese (maximum) 0.05 mg/l
Copper

none allowed

Oil & H2S

none allowed

Polyphosphate

none allowed

Silica (maximum)

10 ppm

Standards

Independent scientific testing has confirmed Template Assisted

Crystallization (TAC) technology provides scale reduction of over

95+%. Testing was conducted under protocol based on DVGW

W512 test to access control of scale formation.

D

B

Dimensions — Weights

A

C

E

Model

Dimensions

Weight

A

B

C

D

E

in.

mm

in.

mm

in.

mm

in.

mm

in.

mm

lbs.

kgs

OF110-1

14

1

2

37

4

1

2

11

5

1

8

13

6

5

8

17

2

1

2

6

5

2.3

OF120-2

24

1

2

62

4

1

2

11

5

1

8

13

6

5

8

17

2

1

2

6

8

3.6

OF140-4

26

66

7

3

4

20

8

5

8

22

9

13

16

25

5

3

4

15

18

8.2

The overall height and the height of the inlet fitting varies due to material variations and assembly
tolerances. Please allow additional clearance above the tank for making connections.

ES-OF110_120_140 1140

© 2011 Watts

USA: No. Andover, MA • Tel: (978) 688-1811 • Fax: (978) 794-1848 • www.watts.com

Canada: Burlington, ON • Tel: (905) 332-4090 • Fax: (905) 332-7068 • www.wattscanada.ca

A Watts Water Technologies Company