VII. Trouble Shooting

PROBLEM

CAUSE

SOLUTION

No hot water at faucet

Boiler does not operate

Refer to boiler installation instructions

Check main service switch

Check fused disconnect

Circulator does not operate

Check power supply

Check shaft coupling

Improper aquastat setting or calibration

Turn tank aquastat to higher setting

Zone valve does not open (if used)

Check power supply

Electrical problem (relay, wiring, fuse, etc.)

Check fuse and replace

Check circuit breaker and reset (if applicable)

Check power supply

Scale build-up

If boiler, circulator and tank are operating satisfactorily, coil
may have scale coating. See Section VI: Service Instructions

Clogged cold water filter or boiler supply
strainer (if used)

Clean or replace filter or strainer

Insufficient hot water

Aquastat setting too low

Adjust aquastat to higher setting

Undersized boiler with no priority to
domestic hot water

Rewire for priority

Peak use of hot water is greater than tank
storage capacity

Determine peak usage and compare to tank volume

Scale build-up

If boiler, circulator and tank are operating satisfactorily, coil
may have scale coating. See Section VI: Service Instructions

Faulty tank aquastat

Replace aquastat

Water at faucet too hot

Aquastat set too high

Lower aquastat setting

Improper system plumbing

Compare plumbing to Section III: Piping

Improper system wiring

Compare wiring to Section IV: Electrical

Boiler cycles more
than 5 times per
day in summer

Excessive demand

Reduce demand or consider larger tank

Faulty aquastat

Replace aquastat

Boiler high limit set too low

Increase boiler high limit setting

Scale Build-up

If boiler, circulator and tank are operating satisfactorily, coil
may have scale coating. See Section VI: Service Instructions