What overload protection device size is
required for a 460 Volt, 3-phase, 15 HP
induction motor with a nameplate current
rating of 19.2 Amps and a 1.0 service fac-
tor? What is the required overload rating
at 125% (for a 1.15 service factor)?
Steps
Keystrokes
Display
Clear calculator
o o
0.
Set to 3-phase
S 3
3 PH
Enter Volts
4 6 0 U VOLT 460.
Enter Horsepower
1 5 h
IND 15. HP
Enter nameplate
current
1 9 ¥ 2 A
AMPS 19.2
Find overload size
L
AMPS 22.08 ol
Display % used
L
%FLC 115.
Find 125% load
1 2 5 L AMPS 24. ol
Display % used
L
%FLC 125.
Reset overload
rating and clear
1 1 5 L o
0.
Overload Protection Size
See also other documents in the category Calculated Industries Calculators, organizers:
- 4215 (64 pages)
- 4225-B (52 pages)
- 4225-C (52 pages)
- 44060 (134 pages)
- 4050 Metric Edition (44 pages)
- 4050 (52 pages)
- 4050 v3.1 (52 pages)
- 4050-F (52 pages)
- 4054 (52 pages)
- 4045-B (54 pages)
- 4045 (26 pages)
- 4067 Pocket Reference Guide (52 pages)
- 4067 User Guide (23 pages)
- 4065 v3.0 (108 pages)
- 4065 v3.1 Pocket Reference Guide Construction Master Pro (39 pages)
- 4065 v3.1 Pocket Reference Guide Advanced Consnruction-Math (40 pages)
- 4065 v3.1 User Guide (110 pages)
- 8030 (44 pages)
- 5025 (48 pages)
- 5070-A Pocket Reference Guide (45 pages)
- 5070-B Pocket Reference Guide (46 pages)
- 5070-A User Guide (66 pages)
- 5070-B User Guide (66 pages)
- 4315 (56 pages)
- 4320 (51 pages)
- 4325 (53 pages)
- 4090 (123 pages)
- 4019 (40 pages)
- 4018 (38 pages)
- 4015 (84 pages)
- 4020 (39 pages)
- 4095-A Pocket Reference Guide (36 pages)
- 4095-B Pocket Reference Guide (38 pages)
- 4095-C Pocket Reference Guide (23 pages)
- 4095-A User Guide (50 pages)
- 4095-B User Guide (68 pages)
- 4095-C User Guide (65 pages)
- 4094 Pocket Reference Guide (38 pages)
- 4094 User Guide (44 pages)
- 8545 (48 pages)
- 4400 (50 pages)
- 8015 (64 pages)
- 8020 (52 pages)
- 8025 (47 pages)