Bosch 250 SXO NG User Manual
Page 21
6 720 607 440
Troubleshooting
21
Display
Cause
Solution
E9
Temperature limiter opened circuit (overheat).
Trips at 220F (104C).
Check connections. *
Check heat exchanger condition.*
EA
No ionization during safety time (safety time out).
Note: appliance makes 3 ignition attempts
before entering error mode “EA”.
Check gas pressure.
(see chapter
2.9
)
*
Check that gas is not diluted with air, as a
result from recent gas pipeline rework.*.
Check if vent terminal is blocked (especially
when the appliance starts up for some sec-
onds and then looses ionization signal).*
Check ionization electrode.*
Check for a proper ground.*
Check CO
2
levels.* (see chapter 9)
EC
The ionization signal momentarily disappeared
more then 5 times in less then 30 seconds. CO
2
may be out of adjustment
FA
Leakage error (gas valves do not close gas
circuit).
Check gas valve and control unit.*
F7
Ionization error (flame sensing at stand-by).
Check control unit.*
E0
Internal software/hardware failure.
Check control unit.*
A7
Hot water temperature sensor/receiver defect
(from control unit).
Check water temperature sensor/receiver and
connections.*
Check incoming water temperature to heater, it
must be above 32°F (0°C)
A9
(flashing)
Hot water temperature sensor/receiver mis-
assembled (from control unit).
Note: if display shows “A9” flashing, the
appliance can be operated normally, but
performance may be affected.
Check that the water temperature sensor/receiver is
properly assembled on the horizontal of the hot
water pipe.*
Check that the water temperature sensor/receiver is
free from corrosion or moisture.*
C1
FAN rotation too low at start-up (from control
unit).
Check supply voltage.*
Check fan and connections.*
Check control unit.*
Check if vent terminal is blocked.*
C6
FAN rotation too low at operation (from control
unit).
Check supply voltage.*
Check fan and connections.*
Check control unit.*
C7
No rotational speed sensor signal from FAN
Check fan and connections.*
Check control unit.*
CA
Water flow signal over specified maximum value
Check water valve and flow sensor.*
E2
Inlet temperature sensor fault
Check water temperature sensor/receiver and
connections.*
Check incoming water temperature to heater, it
must be above 32°F (0°C)
A2
Overheat protection fault
Check connections to the overheat protection.*
Check sensor continuity.*
Check heat exchanger sealings and walls.*
Table 5
* By installer or service technician only.