B. Locate Unit

For service access and unrestricted airflow, provide clearance
on each end and side of unit. Position unit so that there is
unrestricted airflow above unit.

NOTE: Before mounting unit, remove holddown brackets and
release skid.

If conditions or local codes require unit to be fastened to pad,
use the mounting holes in the base rails.

C. Mount Unit

The unit may be mounted on a solid, level concrete pad, on
accessory mounting legs, or on field-supplied raised supports
at each mounting position. (Note that mounting hardware is
field supplied.)

Bolt unit securely to pad or supports after unit is in position
and is level. Be sure to mount unit level to ensure proper oil
return to compressors. Mounting holes on unit can be used to
secure unit to vibration isolators, if required.

1-1/2

38-1/2

1-1/2

TOP

FRONT

33

35

33

38-1/2

Line & Low
Voltage Wiring
Entrances

1-1/2

1-1/2

4-1/4

2-1/2

1-1/8

2-1/8

5-3/4

9-3/4

1-1/2

BOTTOM

REAR

27

24

33

35

A

B

D

C

7/8
4 PLACES

24 1/2

10

19 3/8

4 7/8

FRONT

CONTROL BOX

Fig. 1 — 575B072 Unit Dimensions

NOTES:

1. All dimensions are in inches.
2. Recommended clearance for proper airflow (local codes or jurisdictions may prevail):

Top — 60 in.
Sides — 24 in. on 3 sides, one side may be 6 in. (Control box side should have 24-in. clearance for service
access.)

3. Corner Weights (lb): A = 86

B = 84
C = 92
D = 90