beautypg.com

Bryant 575C User Manual

Page 18

background image

18

SEQUENCE OF OPERATION

I. 575B072 UNITS

When power is supplied to unit, the transformer (TRAN) and
crankcase heater (CCH) are energized.

A. Cooling

On a call for cooling, the thermostat completes the following
circuits: R-G, R-Y, and R-O. If the compressor recycle delay of
3 minutes is complete, the compressor and outdoor fan start.
The reversing valve is energized for cooling and the indoor-
fan motor starts.

When the thermostat is satisfied, the circuits are opened,
and the compressor, outdoor-fan motor, and indoor-fan motor
stop. The reversing valve is deenergized.

B. Heating

On a call for heating, the thermostat completes the following
circuits: R-G and R-Y. If the compressor recycle delay of
3 minutes is complete, the compressor and outdoor fan start.
The indoor-fan motor will also start.

If room temperature continues to fall, the thermostat
completes circuit R-W. If the optional electric heat package is
used, the heat relay is energized, and the electric heaters are
energized.

When the thermostat is satisfied, the circuits are opened,
and the compressor, outdoor-fan motor, heaters, and indoor-
fan motor stop.

C. Defrost

Defrost board (DB) is a time and temperature control, which
includes a field-selectable time period between checks for
frost (30, 50, and 90 minutes). Electronic timer and defrost
cycle start only when contactor is energized and defrost ther-
mostat (DFT) is closed (below 28 F).

Defrost mode is identical to Cooling mode, except outdoor-fan
motor (OFM) stops and a bank of supplemental electric heat
turns on to warm air supplying the conditioned space.
Defrost mode is terminated when the DFT reaches 65 F.

D. Air Circulation

When the fan switch is at FAN ON, the indoor-air fans oper-
ate continuously to provide ventilation. The thermostat
operates the other components as described above.

E. Emergency Heat Cycle

If the compressor is inoperative due to a tripped safety
device, the second stage of the thermostat automatically
energizes the indoor-air fan and the electric resistance heat-
ers (if equipped).

II. 575C090,120 UNITS

When power is supplied to unit, the transformer (TRAN) is
energized. The crankcase heater is also energized.

A. Cooling

With the thermostat subbase in the cooling position, and
when the space temperature comes within 2° F of the cooling
set point, the thermostat makes circuit R-O. This energizes
the reversing valve solenoid (RVS) and places the unit in
standby condition for cooling.

As the space temperature continues to rise, the second stage
of the thermostat makes, closing circuit R-Y. When compres-
sor time delay (5 ± 2 minutes) is completed, a circuit is made
to contactor (C), starting the compressor (COMP) and
outdoor-fan motor (OFM). Circuit R-G is made at the same
time, energizing the indoor-fan contactor (IFC) and starting
the indoor-fan motor (IFM) after one-second delay.

Fig. 19A — 575B072 Charging Chart

Fig. 19B — 575C090,120 Charging Chart

50

LIQUID PRESSURE AT LIQUID VALVE (PSIG)

LIQUID

TEMPERA

TURE

A

T

LIQUID V

A

L

VE (F)

344

LIQUID PRESSURE AT LIQUID VALVE (Kilopascals)

ADD CHARGE IF ABOVE CURVE

REDUCE CHARGE IF BELOW CURVE

50

60

70

80

90

100

110

120

130

140

100

150

200

250

300

350

400

689

1034

1379

1724

2069

2414

LIQUID

TEMPERA

TURE

A

T

LIQUID V

A

L

VE (C)

10

16

21

27

32

38

43

49

54

60

Fig. 19C — 541A180 Charging Chart