Kpc capacitor bank installation instruction – TCI KPC User Manual
Page 2
KPC Capacitor Bank
Installation Instruction
INPUT
When installing the KPC capacitor
bank on the INPUT side of the Variable
Frequency Drive (VFD) or induction
motor, please use the following guidelines
when wiring the unit:
The KPC capacitor bank is wired in
parallel with the load.
Refer to NEC wiring practices for
appropriate wire sizes for your application.
Power Wiring: Only use 75°C
copper conductors unless the wire
connector is marked for Al/Cu, then the
use of aluminum wire is permitted.
In standard 40°C ambient or less
installations, a clearance of 3 inches on
all sides of the capacitor bank and its
enclosure is recommended for assisting in
heat dissipation and ample wire bending
space.
These capacitors are designed to be
panel mounted.
Field Wiring Information
Below are typical wiring diagrams for
the 3-phase KPC applied to the Variable
Frequency Drive (VFD) or motor.
3-phase and 1-phase, 600 Volt Class
UL Listed; File E-116124
kVar rated device
Ambient Temperature: 40°C
Product Specifications
Wiring Diagram
Line
VFD or
Motor
A
B
C
Wiring Diagram with Tuning Reactor
Line
VFD or
Motor
A
B
C
If tuning
reactor
used
Optional Thermal Switch
Wiring: KPC has 3 power terminals, 1 for each
phase of 3 phase circuit. Wire in any order.
Up
to 40
Kvar
80
Kvar
180
Kvar
240
Kvar
300
Kvar
H (in.) for encl
17.4
28.0
52.0
70.0
72.0
W (in.) for encl
17.0
17.0
17.0
20.0
36.0
D (in.) for encl
12.3
12.3
16.3
20.0
24.0
Vent Area top (in2) 24.0
55.0
76.0
57.5
75.0
Vent Area bottom
(in2)
21.0
10.0
28.5
50.0
112.5
Required Minimum Dimensions
if product is enclosed: