SET THERMOSTAT TO CALL FOR HEAT
APPLY 120 VOLTS - GREEN LIGHT IS ON
CHECK 120V TO DSI AT “L1”
CHECK 120V OUT AT “IND” FROM DSI TO BLOWER
COMBUSTION AIR BLOWER STARTS
AIR PROVING SWITCH HAS CLOSED 24
VOLTS IS PRESENT AT “PSW” AT DSI
CONTROL.
CHECK TUBING TO SWITCH IS CONNECTED AND
NOT BLOCKED OR KINKED
CHECK AIR PRESSURE WITH MANOMETER
CHECK FOR OBSTRUCTION IN THE AIR INTAKE
REPLACE DEFECTIVE BLOWER
CHECK INTEGRITY OF SWITCH
REPLACE DEFECTIVE SWITCH
CHECK DSI CONTROL FUSE FOR CONTINUITY
VISIBLY CHECK IF IGNITER IS SHORTING OUT
CHECK GROUND WIRING
REMOVE AND INSPECT IGNITER AND LEAD
CHECK BOOT OF THE IGNITION CABLE FOR SIGNS
OF MELTING OR OVERHEATING
IF “YES” ... TAKE PROTECTIVE ACTION TO SHIELD
CABLE AND BOOT FROM EXCESSIVE TEMPERA-
TURE; REPLACE ANY DEFECTIVE COMPONENT
CHECK CERAMIC INSULATOR AND CAP
CHECK SPARK GAP SETTING IS 3/16” (ADJUST BY
MOVING THE GROUND PRONG ONLY)
PERFORM IGNITION LEAD TEST (See SPARK IGNI-
TION CIRCUIT INSTRUCTIONS—Section 22)
GOOD SPARK.....REPLACE IGNITER
NO SPARK/OR WEAK.....REPLACE CONTROL
SPARK IGNITER / SENSOR
24V TO GAS VALVE - RED LIGHT IS ON
CONTINUED
SEQUENCE OF EVENTS (also see DSI Troubleshooting previous page)
22. TROUBLESHOOTING GUIDE — HEATER OPERATION — FENWAL DSI
NO
YES
WARNING
Improper adjustment, alteration, service or maintenance can
cause property damage, injury or death. This heater must be
installed and serviced only by a trained gas service technician
YES
YES
NO
NO
REMEDY 120 VOLTS SUPPLY FAULT
NO
NO
FAULTY RELAY SWITCH IN DSI — REPLACE DSI
BLOCKED FLUE SWITCH IS CLOSED
24 VOLTS IS PRESENT AT “TH” AT DSI
CONTROL.
AMBER LIGHT IS ON
YES
NO
CHECK TUBING TO SWITCH IS CONNECTED AND
NOT BLOCKED OR KINKED
CHECK AIR PRESSURE WITH MANOMETER
CHECK INTEGRITY OF SWITCH
REPLACE DEFECTIVE SWITCH
CHECK FOR AND REMEDY ANY OBSTRUCTION IN
THE VENT / TUBE