Schwank supraSchwank User Manual
Page 7
supra/primo Manual
IM091112
RD: APR 2013
RL: 13B
7
SUSPENDED AT AN ANGLE OF 30° *: Measured from outer surface of heater
SUSPENDED HORIZONTALLY: Measured from outer surface of heater
MOUNTING CLEARANCE TO COMBUSTIBLES
MODEL
BELOW ‘C’
Inches [cm]
SIDES ‘S’
Inches [cm]
TOP ‘A’
Inches [cm]
ENDS ‘E’
Inches [cm]
primoSchwank 10
primoSchwank 15
primoSchwank 20
primoSchwank 30
90" [229]
96" [244]
100" [254]
105” [267]
30” [76]
30” [76]
36” [91]
42” [107]
18" [46]
18" [46]
18" [46]
18" [46]
48" [122]
48" [122]
48" [122]
48" [122]
supraSchwank 10
supraSchwank 15
supraSchwank 20
supraSchwank 30
90" [229]
96" [244]
100" [254]
105” [267]
30” [76]
30” [76]
33” [84]
36” [91]
16” [41]
16” [41]
16” [41]
16” [41]
48" [122]
48" [122]
48" [122]
48" [122]
FIGURE 1: MINIMUM DISTANCES TO COMBUSTIBLES - refer to
Table 1 for values
NOTE: A ‘PEEL & STICK’ SIGN IS SUPPLIED:
USE AN INDELIBLE MARKER TO
ENTER VALUES ‘H’, ‘S’, ‘F’, & ‘B’ ON .
POST THE SIGN ADJACENT TO THE HEATER THERMOSTAT OR IN A
PROMINENT LOCATION.
See next page for details.
C
A
A
S
S
SUSPENDED
HORIZONTALLY
C
A
A
F
B
SUSPENDED
AT 30°
TABLE 1: MINIMUM CLEARANCE TO COMBUSTIBLES
MODEL
BELOW ‘C’
Inches [cm]
FRONT ‘F’
Inches [cm]
BACK ‘B’
Inches [cm]
TOP ‘A’
Inches [cm]
ENDS ‘E’
Inches [cm]
primoSchwank 10
primoSchwank 15
primoSchwank 20
primoSchwank 30
67” [170]
66” [168]
70” [178]
74” [188]
67” [170]
66” [168]
70” [178]
74” [188]
8” [20]
8” [20]
8” [20]
8” [20]
24” [61]
24” [61]
24” [61]
24” [61]
48" [122]
48" [122]
48" [122]
48" [122]
supraSchwank 10
supraSchwank 15
supraSchwank 20
supraSchwank 30
66” [168]
66” [168]
69” [175]
72” [183]
66” [168]
66” [168]
69” [175]
72” [183]
8” [20]
8” [20]
8” [20]
8” [20]
24” [61]
24” [61]
24” [61]
24” [61]
48" [122]
48" [122]
48" [122]
48" [122]
NOTE
: Suspended between horizontal and 30°: Use the largest clearance from each column
~ See additional notes on previous & next pages ~
T = Site distance
to floor
Site distance to floor = T