Schwank supraSchwank User Manual
Page 7

supra/primo Manual
IM091112
RD: APR 2013
RL: 13B
7
SUSPENDED AT AN ANGLE OF 30° *: Measured from outer surface of heater
SUSPENDED HORIZONTALLY: Measured from outer surface of heater
MOUNTING CLEARANCE TO COMBUSTIBLES
MODEL
BELOW ‘C’
Inches [cm]
SIDES ‘S’
Inches [cm]
TOP ‘A’
Inches [cm]
ENDS ‘E’
Inches [cm]
primoSchwank 10 
primoSchwank 15 
primoSchwank 20 
primoSchwank 30 
 90" [229] 
 96" [244] 
100" [254] 
105” [267]
30” [76] 
30” [76] 
36” [91] 
42” [107] 
18" [46] 
18" [46] 
18" [46] 
18" [46] 
48" [122] 
48" [122] 
48" [122] 
48" [122] 
supraSchwank 10 
supraSchwank 15 
supraSchwank 20 
supraSchwank 30 
 90" [229] 
 96" [244] 
100" [254] 
105” [267]
30” [76] 
30” [76] 
33” [84] 
36” [91] 
16” [41] 
16” [41] 
16” [41] 
16” [41] 
48" [122] 
48" [122] 
48" [122] 
48" [122] 
FIGURE 1: MINIMUM DISTANCES TO COMBUSTIBLES - refer to
Table 1 for values
NOTE: A ‘PEEL & STICK’ SIGN IS SUPPLIED:
USE AN INDELIBLE MARKER TO
ENTER VALUES ‘H’, ‘S’, ‘F’, & ‘B’ ON . 
POST THE SIGN ADJACENT TO THE HEATER THERMOSTAT OR IN A 
PROMINENT LOCATION. 
See next page for details.
C
A
A
S
S
SUSPENDED 
HORIZONTALLY 
C
A
A
F
B
SUSPENDED
AT 30°
TABLE 1: MINIMUM CLEARANCE TO COMBUSTIBLES
MODEL
BELOW ‘C’
Inches [cm]
FRONT ‘F’
Inches [cm]
BACK ‘B’
Inches [cm]
TOP ‘A’
Inches [cm]
ENDS ‘E’
Inches [cm]
primoSchwank 10 
primoSchwank 15 
primoSchwank 20 
primoSchwank 30 
67” [170] 
66” [168] 
70” [178] 
74” [188] 
67” [170] 
66” [168] 
70” [178] 
74” [188] 
8” [20] 
8” [20] 
8” [20] 
8” [20] 
24” [61] 
24” [61] 
24” [61] 
24” [61] 
48" [122] 
48" [122] 
48" [122] 
48" [122] 
supraSchwank 10 
supraSchwank 15 
supraSchwank 20 
supraSchwank 30 
66” [168] 
66” [168] 
69” [175] 
72” [183] 
66” [168] 
66” [168] 
69” [175] 
72” [183] 
8” [20] 
8” [20] 
8” [20] 
8” [20] 
24” [61] 
24” [61] 
24” [61] 
24” [61] 
48" [122] 
48" [122] 
48" [122] 
48" [122] 
NOTE
: Suspended between horizontal and 30°: Use the largest clearance from each column
~ See additional notes on previous & next pages ~
T = Site distance
to floor
Site distance to floor = T
