beautypg.com

Scan Tech HFW Power Generator User Manual

Scan Tech Equipment

background image

 

Scan Tech AS

Finnestadsvingen 23

Po.Box. 738

Tel.

+47 51 54 54 00

[email protected]

4029 Stavanger 4001 Stavanger Fax +47 51 54 54 50 www.scan-tech.no









Model 

Engine 

Power 

kVA               kW 

P.R.P(1)S.By(2)P.R.P(1) S.By(2) 

Gov. 

(3)

 

Cyl

Feed.

(4) 

Dimensions mm.**

L             W           H 

Weight** 

Kg 

Fuel 

Tank Ltr 

Fuel Cons.*

L/h. 

HFW‐60 T5 

NEF45 SM 1A 

60 

63 

48 

50 

4L 

TC 

2 750 

1 100 

1 500 

1 525 

175 

13,7 

HFW‐75 T5 

NEF45 SM 2A 

73 

80 

58 

64 

4L 

TC 

2 750  

1 100 

1 500 

1 550 

175 

17,1 

HFW‐100 T5 

NEF45 TM 2A 

100 

108 

80 

86 

4L 

TCA 

2 750 

1 100 

1 500 

1 670 

175 

22,0 

HFW‐135 T5 
 

NEF67 TM 2A 

130 

143 

104 

114 

6L 

TCA 

3 300 

1 200 

1 800 

2 295 

245 

29,0 

HFW‐160 T5 

NEF67 TM 3A 

160 

175 

128 

140 

6L 

TCA 

3 300 

1 200 

1 800 

2 365 

245 

36,0 

HFW‐180 T5 

NEF67 TE 2A 

180 

194 

144 

155 

6L 

TCA 

3 300 

1 200 

1 800 

2 390 

245 

‐ 

HFW‐200 T5 

NEF67 TE 2A 

200 

220 

160 

176 

6L 

TCA 

3 300 

1 200 

1 800 

2 435 

245 

41,3 

HFW‐250 T5 

C87 TE 1D 

250 

275 

200 

220 

6L 

TCA 

3 800 

1 400 

2 105 

3 840 

445 

‐ 

HFW‐305 T5 

C10 TE 1D 

300 

330 

240 

264 

6L 

TCA 

4 100 

1 600 

2 210 

4 135 

590 

‐ 

HFW‐350 T5 

C13 TE 2S 

350 

390 

280 

312 

6L 

TCA 

4 100 

1 600 

2 210 

4 295 

590 

‐ 

HFW‐400 T5 

C13 TE 3S 

400 

440 

320 

352 

6L 

TCA 

4 100 

1 600 

2 210 

4 480 

590 

‐ 

 
*Fuel consumption measured in ltr/hr. at 100% load at 1500 rpm at 50Hz.

 

**Weights and dimensions are subject to variations depending to the 
generators configuration solicited by the customer. 
To be consulted by Scan Tech. 
 
Ambient reference conditions: 
1 000 mbar, 25°C, 30% relative humidity. Rating according to ISO 3046 
 
1 – P.R.P. Prime Power – ISO 8528: Prime power is the maximum power 
available during a variable power sequence, which may be run 
for an unlimited number of hours per year, between stated maintenance 
intervals.The permissible average power output during a 24 hours period 
shall not exceed 80% of the prime power.10% overload available for 
governing purposes only. 
 
2 – Standby power (ISO 3046 Fuel Stop power): Power available for use at variable loads for limited annual  
time (500h), within the following limits of maximum operatingtime: 100% loads 25h per year – 90% loads  
200h per year. No overload available. 
Applicable in case of failure of the main in areas of reliable electrical network. 
 
3 – M= Mechanical speed governor. 
        E= Electronic speed governor. 
 
4 – TC = Turbocharged; TCA = Turbocharged and aftercooled. 
 

Scan Tech reserve the right of modify any characteristic without prior notice. Weights and dimensions based on products standards and sec / illustrations may include optional equipment. 
Technical data here described correspond with the available information of the moment of printing. Industrial design under patent.