Specifications continued – Bryant DELUXE 11 SEER R-410A User Manual
Page 5
—5—
SPECIFICATIONS Continued
* Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure.
† If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).
The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26. If
other than uncoated (non-plated), 60 or 75°C (140 or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is
used, consult applicable tables of the NEC (ANSI/NFPA 70).
‡ Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.
** Fan motor with ball bearings required.
†† See low-ambient controller Installation Instructions for application.
N/A — Not Applicable.
NOTE:
Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.
UNIT SIZE-SERIES
042-A
048-A
060-A
Operating Weight (Lb)
215
217
278
ELECTRICAL
Unit Volts—Hertz—Phase
208/230-60-1
Operating Voltage Range*
187-253
Compressor—Rated Load Amps
19.9
24.4
30.1
Locked Rotor Amps
127.0
131.0
172.0
Condenser Fan Motor—Full Load Amps
1.10
1.40
1.40
Min Unit Ampacity for Wire Sizing
24.4
26.7
35.9
Min Wire Size (60°C Copper) AWG†
10
8
8
Min Wire Size (75°C Copper) AWG†
10
10
8
Max Wire Length (Ft) (60°C Copper)‡
77
97
80
Max Wire Length (Ft) (75°C Copper)‡
73
59
76
Max Branch Circuit Fuse or
Circuit Breaker Size (Amps)
40
50
60
COMPRESSOR & REFRIGERANT
Compressor— Type
Scroll
Manufacturer
Copeland
Temperature & Current Protection
Internal Line Break
Refrigerant—Type
Puron® (R-410A)
Amount (Lb)
6.33
6.83
7.93
CONDENSER COIL & FAN
Coil Face Area (Sq Ft)
12.16
12.16
18.3
Fins per In.—Rows—Circuits
25—1—2
25—1—2
25—1—3
Fan Motor—HP (PSC) & RPM
1/5 & 825
1/4 & 1100
1/4 & 1100
Volts—Hertz—Phase
208/230-60-1
Condenser Airflow (CFM)
2800
3400
3400
OPTIONAL EQUIPMENT
Support Feet
KSASF0101AAA
Coastal Filter
KAACF0801MED
Time Delay Relay
KAATD0101TDR
Cycle Protector
KSACY0101AAA
Crankcase Heater
KAACH1201AAA
Start Assist—Capacitor/Relay Type
KSAHS1501AAA
KSAHS1601AAA
Start Assist—PTC Type
KAACS0201PTC
TXV (Hard Shutoff)
KSATX0301HSZ
KSATX0401HSZ
KSATX0501HSZ
Piston Body
KSAPX0101PIS
Filter Drier (Suction Line) (RCD)
KH45LG141
Evaporator Freeze Thermostat††
KAAFT0101AAA
Liquid-Line Solenoid Valve
KAALS0201LLS
Winter Start Control††
KAAWS0101AAA
Low-Ambient Pressure Switch
KSALA0301410
MotorMaster® Control**
32LT660004
Ball Bearing Fan Motor (RCD)
HC38GE231
HC40GE232
Thermostat—Auto Changeover,
Non-Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
TSTATBBNAC01-B
Thermostat—Auto Changeover,
7-Day Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
TSTATBBPAC01-B
Thermidistat™ Control—
Programmable Thermostat with Humidity Control
TSTATBBPRH01-B
Builder’s Thermostat—Manual Changeover,
Non-Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
TSTATBBBAC01-B
Outdoor Air Temperature Sensor
TSTATXXSEN01-B
Backplate for Non-Programmable Thermostat
TSTATXXNBP01
Backplate for Programmable Thermostat
TSTATXXPBP01
Backplate for Builder’s Thermostat
TSTATXXBBP01
Thermostat Conversion Kit (4 to 5 wire)—10 Pack
TSTATXXCNV10