Model GD-K7D2 (115 VAC) Sample Draw Transmitter • 1
Overview
This manual describes the 115 VAC version of the Model GD-K7D2 sample draw 4 - 20
mA transmitter detector head. This manual also describes how to install, start up,
maintain, and calibrate the GD-K7D2 when it is used with a gas monitoring controller. A
parts list at the end of this manual lists replacement parts and accessories for the
GD-K7D2.
Specifications
Table 1 lists specifications for the 115 VAC version of the GD-K7D2.
WARNING: When using the GD-K7D2, you must follow the instructions and warnings
in this manual to assure proper and safe operation of the GD-K7D2 and to
minimize the risk of personal injury. Be sure to maintain and periodically
calibrate the GD-K7D2 as described in this manual.
Table 1: Specifications
Target Gas & Detector Range
Refer to the RKI Instruments Inc. List of Detectable Gasses
Area Classification
Indoor, non-hazardous locations
Sampling Method
Sample-draw
Input Power
• 115 VAC (for pump)
• 24 VDC (for detection circuitry)
Signal Output
4 to 20 mA
Response Time
90% in 60 seconds
Accuracy
± 10% of reading or ± 5% of full scale (whichever is greater)
Flow Rate
Approximately 0.5 liters/minute
Recommended Sample Tubing
4 mm I.D. x 6 mm O.D. Teflon PTFE
Recommended Sample Tubing Length
See Table 2 in the Installation section on p. 10