Model GD-70D4S-XX Sample Draw Transmitter • 4

Figure 3: Factory Wiring

Installation

This section describes how to install the GD-70D4S-XX at the monitoring site.

Mounting the GD-70D4S-XX

1.

Select a mounting site that is representative of the monitoring environment. Consider
the following when you select the mounting site.

Select a site that is easily accessible for servicing.

Select a site where the GD-70D4S-XX is not likely to be bumped or disturbed.
Make sure there is sufficient room to make wiring and sample line connections at
the bottom of the GD-70D4S-XX. Also make sure there is sufficient room to
perform start-up, maintenance, and calibration procedures.

Select a site near the sampling area. The GD-70D4S-XX is designed to detect a
variety of toxic gases many of which are easily absorbed in sample tubing. Keep
the sample line length to a minimum. Teflon PTFE tubing is recommended.

Use four 1/4” screws through the mounting feet to mount the GD-70D4S-XX to a
vertical surface. See Figure 4 for the mounting dimensions.