Parts list – RKI Instruments 65-2485RK-02 User Manual
Page 24

20 • 65-2485RK-02 Multi Point Detector
Returning to Normal Operation
1.
Unscrew the calibration cup from the oxygen detector.
NOTE:
For convenience, leave regulator and calibration cup connected by the sample
tubing.
2.
When the controller display reading rises above the alarm points, return the
controller to normal operation.
NOTE
: If you do not allow the gas reading to rise above the alarm points, then unwanted
alarms may occur.
3.
Verify that the controller display reading increases and stabilizes at 20.9% oxygen.
4.
Store the components of the calibration kit in a safe and convenient place.
Parts List
Table 5 lists replacement parts and accessories for the multi-point detector.
Table 3: Parts List
Part Number
Description
06-1248RK-03
Calibration kit sample tubing, 3 ft. length
07-0033RK
Detector housing cap gasket (for H
2
S, O
2
and CO detectors)
07-0203RK
Rubber retaining boot (for CO and H
2
S detectors)
14-2101RK
Spacer between H
2
S sensor and rubber boot
33-7101RK
Charcoal filter disk (for CO detector)
65-1025RK
Oxygen replacement plug-in sensor
65-2423RK-05
H
2
S replacement detector assembly (includes sensor)
65-2433RK-05
CO replacement detector assembly (includes sensor)
65-2485RK-02
Multi-point detector assembly, O
2
/H
2
S/CO
65-2514RK
Oxygen replacement detector assembly (includes sensor)
71-0237RK
65-2485RK-02 Multi Point Detector Operator’s Manual (this document)
81-0064RK-01
Calibration cylinder, 50 ppm CO in air, 34 liter steel
81-0064RK-03
Calibration cylinder, 50 ppm CO in air, 103 liter steel
81-0076RK
Zero air calibration cylinder, 17 liter steel
81-0076RK-01
Zero air calibration cylinder, 34 liter steel
81-0076RK-03
Zero air calibration cylinder, 103 liter steel