65-2405RKSS Combustible Gas Transmitter • 1
Overview
This manual describes the 65-2405RKSS combustible gas transmitter. This manual also
describes how to install, start up, configure, maintain, and calibrate the transmitter when
it is used with a gas monitoring controller. A parts list at the end of this manual lists
replacement parts and accessories for the combustible gas transmitter.
Specifications
Table 1 lists specifications for the combustible gas transmitter.
WARNING: When using the 65-2405RKSS, you must follow the instructions and
warnings in this manual to assure proper and safe operation of the
65-2405RKSS and to minimize the risk of personal injury. Be sure to
maintain and periodically calibrate the 65-2405RKSS as described in this
manual.
Table 1:Specifications
Description
Specification
Target Gas
Combustible gas, methane calibration standard
1
Area Classification
Explosionproof for Class I, Groups B, C, and D
Sampling Method
Diffusion
Signal Output
4 to 20 mA
Detection Range
0 to 100% LEL
Accuracy
± 5% of reading or ± 2% LEL (whichever is greater)
Response Time
90% in 45 seconds
1
If calibration to a combustible gas other than methane is required, specify the required
calibration gas at time of order.