65-2398RK Combustible Gas Transmitter • 17
4.
Turn the regulator’s on/off knob clockwise to close the regulator.
5.
Unscrew the regulator from the calibration cylinder.
Returning to Normal Operation
1.
Remove the voltmeter leads from the amplifier test points.
2.
Unscrew the calibration cup from the detector.
NOTE:
For convenience, leave the regulator and calibration cup connected by the
sample tubing.
3.
Secure the junction box cover to the junction box.
4.
When the controller display reading falls below the alarm setpoints, return the
controller to normal operation.
5.
Verify that the controller display reading decreases and stabilizes at 0 %LEL.
6.
Store the components of the calibration kit in a safe and convenient place.
See also other documents in the category RKI Instruments Sensors:
- Eagle Series (66 pages)
- Eagle Series (89 pages)
- 01 Series Manual (33 pages)
- 01 Series Quik Start (2 pages)
- OX-94 (13 pages)
- FP-3 (16 pages)
- GasWatch 1 (18 pages)
- GasWatch 2 Manual (37 pages)
- GasWatch 2 Quik Start (2 pages)
- GP-01 (34 pages)
- GP-01 with self resetting alarms (33 pages)
- GP-204 (7 pages)
- NP-204 (13 pages)
- RI-215A (24 pages)
- SC-01 (45 pages)
- SC-01 (68 pages)
- Data Cal 2000 (88 pages)
- EAGLE 2 Manual (309 pages)
- Eagle 2 Quik Start (2 pages)
- GX-94 (3 pages)
- GX-94 (52 pages)
- SDM-E2 (89 pages)
- SDM-E2 (224 pages)
- Eagle 1 Manual (89 pages)
- Eagle 1 Quik Start (2 pages)
- Inert Gas Testing Eagle with Two Pumps (66 pages)
- Gas Tracer (234 pages)
- Gas Tracer 10,000 ppm (120 pages)
- GX-2001 Manual (45 pages)
- GX-2001 Quik Start (2 pages)
- GX-2001 Canadian Version (43 pages)
- GX-2003 Manual (94 pages)
- GX-2003 Quik Start (2 pages)
- GX-2009 Manual (73 pages)
- GX-2009 Quik Start (2 pages)
- GX-2009 Supplement (2 pages)
- GX-2012 Manual (185 pages)
- GX-82 (22 pages)
- GX-82A (43 pages)
- GX-86 (22 pages)
- GX-86A (39 pages)
- GX-8000(PT0-098) (52 pages)
- GX-8000(H4-0050) (23 pages)
- RX-516 (36 pages)
- GX-2009 (2 pages)