Installation – RKI Instruments 65-2340RK User Manual

Page 9

background image

65-2340RK Toxic Gas Transmitter • 5

Installation

This section describes procedures to mount the toxic gas transmitter in the monitoring
environment and wire the transmitter to a controller.

Mounting the Toxic Gas Transmitter

1.

Select a mounting site that is representative of the monitoring environment. Consider
the following when you select the mounting site.

Select a site where the transmitter is not likely to be bumped or disturbed. Make
sure there is sufficient room to perform start-up, maintenance, and calibration
procedures.

Select a site where the target gas is likely to be found first.

Figure 3: Mounting the Toxic Gas Transmitter

2.

At the monitoring site you select, hang or mount the junction box with the detector
facing down (see Figure 3).

2.70

.75

0.38

3/4 NPT
Conduit Hub

Rubber
Spacer, 3X

Junction

Box

Toxic
Detector

3.65

9.60 Max