RKI Instruments 65-2336RK User Manual
Page 7

65-2336RK CO Transmitter • 3
CO Detector
The CO detector consists of the detector housing body, detector housing cap, cap gasket,
plug-in sensor, and the charcoal filter.
Figure 2: CO Detector Component Location
Detector Housing Body
The detector housing body protects the electronic components within the housing. Use the
mounting threads at the top of the housing to screw the CO detector into the 3/4” NPT
hub on the bottom of the junction box. Two wires extend from the top of the detector
housing body. Use these wires to connect the CO detector to the amplifier. One of the
wires is red and one of the wires is black.
The housing includes a four-socket pattern. This socket pattern accepts the sensor’s four
pins to secure the sensor within the detector housing. A pre-amplifier, located between the
sockets and two interconnect wires, conditions the sensor’s signal before the signal
reaches the controller.
Housing Cap & Cap Gasket
The housing cap screws onto the detector housing. It retains the plug-in sensor and
protects it from damage. The housing cap also includes a flame arrestor which contains
any sparks that may occur within the detector and a flame arrestor guard which protects
the flame arrestor from damage. Unscrew the detector cap to access the plug-in sensor for
maintenance or replacement. A cap gasket seals the interface between the housing and
cap.
Plug-In CO Sensor
The sensor is secured within the detector assembly by the housing cap. Through a series
of chemical and electrical reactions, the sensor produces an electrical output that
corresponds to the detection range of the transmitter.
Plug-In CO Sensor
Rubber Boot With
Charcoal Filter
Detector Housing Cap
Detector Housing Body
Cap Gasket
Flame Arrestor
Guard