Overview, Specifications – RKI Instruments 61-1001RK-05 User Manual
Page 5
61-1001RK-05 Combustible Gas Detector• 1
Overview
This manual describes the 61-1001RK-05 hydrogen detector (internal amplifier type). This
manual also describes how to install, start up, maintain, and calibrate the detector when it
is used with a gas monitoring controller. A parts list at the end of this manual lists
replacement parts and accessories for the hydrogen detector.
The 61-1001RK-05 hydrogen detector includes the NC-6205-05 hydrogen detector and a
junction box. This manual may also be used for the NC-6205-05 hydrogen detector which
does not include a junction box and is normally mounted in one of a controller’s conduit
hubs. If you are using a NC-6205-05 hydrogen detector, disregard all references to the
junction box and junction box terminal strip.
Specifications
WARNING: Do not use this product in a manner not specified in this instruction
manual.
Table 1 lists specifications for the hydrogen detector.
NOTE:
The following symbol on the detector label is a caution to the user to refer to this
documentation for installation instructions:
WARNING: When using the 61-1001RK-05, you must follow the instructions and
warnings in this manual to assure proper and safe operation of the
61-1001RK-05 and to minimize the risk of personal injury. Be sure to
maintain and periodically calibrate the 61-1001RK-05 as described in this
manual.
Table 1: 61-1001RK-05 Specifications
Description
Specifications
Target Gas
Hydrogen
Area Classification
Explosion proof for Class I, Groups B, C, and D
Sampling Method
Diffusion
Detection Range
0 to 100 %LEL
Response Time
90% in 45 seconds
Accuracy
± 5% of reading or ± 2% LEL (whichever is greater)
!