RKI Instruments Beacon 200 RIg Monitor, H2S/H2S User Manual
Page 29

Beacon 200 Rig Monitor Operator’s Manual • 24
Alarm 2 Condition
This section describes the audible and visual indications for an alarm 2
condition and suggests response to an alarm 2 condition.
Alarm 2 Condition Indications
When the gas reading of an active channel reaches the alarm 2 setpoint,
the Rig Monitor senses an alarm 2 condition. The Rig Monitor alerts you to
an alarm 2 condition as follows:
•
The ALARM 2 light turns on.
•
The gas reading in alarm 2 condition continues to flash and alternates
with the ALARM-2 messages.
•
The buzzer sounds a Pulsing tone.
•
The common alarm 2 relay energizes.
•
The applicable alarm 2 channel relay energizes.
Responding to an Alarm 2 Condition
This section suggests response to an alarm 2 condition.
1. Follow your established procedure for a high level H
2
S condition.
2. Alarms are latching. After the gas reading falls below the alarm 2
setpoint, press the reset switch to reset the alarm circuit. Resetting the
alarm circuit turns off the ALARM 2 light, and de-energizes the
common and channel alarm 2 relays.
NOTE: To silence the buzzer while in an alarm 2 condition, press the
reset switch.
You cannot de-energize the alarm 2 relays until the gas reading
falls below the alarm 2 setpoint.
Fail Condition
This section describes the audible and visual indications for a fail condition
and suggests response to a fail condition.
Fail Condition Indications
The Rig Monitor senses a fail condition for any of the following:
•
The detector head wiring to the Rig Monitor is disconnected or
incorrectly connected.
•
The detector head’s detector is disconnected or incorrectly connected.