3.6 I

NSTALLING THE

D

UCTWORK AND

R

EGISTERS

(

CONT

D

)

3.6.3 S

IMPLIFIED

I

NSTALLATION

(

AS ILLUSTRATED IN

S

ECTION

2.3)

There are 2 methods for connecting the unit to the furnace/air handler:

Method 1: Supply-return connection

Method 2A: Return-return without

Method 2B: Return-return with

Automatic fresh air bypass

Automatic fresh air bypass

Stale air intake

• Cut an opening into the furnace/air handler return duct not less than 10 feet (3.1 m) from the furnace/air handler (A+B).
• Connect this opening to the

Exhaust air from building port of the HRV/ERV.

Fresh air distribution

• Same instructions as for Method 1 or Method 2, Section 3.6.2.

For Method 2 (Return-return), make sure there is a distance of at least 3 feet (0.9 m) between the 2 connections to the furnace/air
handler.
NOTE: For Method 1, it is not essential to synchronize the furnace blower operation with the unit operation, but we recommend it.

3. INSTALLATION

(CONT’D)

CAUTION

If using Method 2, unless the optional Automatic fresh air bypass (part #15391) is installed, make sure the furnace/air handler
blower operation is synchronized with the unit operation! See Section 5.

- 12 -

WARNING

When performing duct connections, always use approved tools and materials. Respect all corresponding laws and/or safety
regulations. Please refer to your local building code.

CAUTION

When performing duct connections to the furnace supply duct, unless using the optional Automatic fresh air bypass
(part #15391), this duct must be sized to support the additional airflow produced by the HRV/ERV. Also, use a steel duct. For a
Return-Return installation, installing the optional Automatic fresh air bypass (part #15391) eliminates the obligation to operate
the furnace blower when the HRV/ERV is in operation.

0

!

B

A

VJ0037

A+B=

NOT LESS

THAN

10’ (3.1

M

)

MINIMUM

18”

(0.5

M

)

STEEL DUCT

B

A

VJ0038

A+B=

NOT LESS

THAN

10’ (3.1

M

)

MINIMUM

3’

(0.9

M

)

VJ0034

A

B

C

D

ISTANCE

A:

MINIMUM

3’ (0.9

M

)

B+C=

NOT LESS THAN

10’ (3.1

M

)

A

UTOMATIC FRESH

AIR BYPASS