PAGE 52 — DCA-400SSK — PARTS AND OPERATION MANUAL (STD)— REV. #3 (09/17/01)

Figure 53. Engine Controller Running

Status LED (OFF)

NEVER stop the engine suddenly except
in an emergency. DO NOT use the
emergency stop switch a as method of
shutting down the engine. This switch is
ONLY to be used in the event of an

emergency.

1. To stop the engine in the event of an emergency, PUSH

the emergency stop button ( Figure 54) inward. This button
is located on the generator's engine operating panel,
see page 30, Figure 11.

Emergency Stop

CAUTION:

Figure 54. Emergency Stop Button

Figure 52. Off/Manual Auto Switch (OFF)

Engine Shutdown
To shutdown the generator use the following procedure:

1. Place both the MAIN, GFCI and LOAD circuit breakers

to the "OFF position".

4. Verify that the "Engine Running" status LED (Figure 53)

on the microprocessor (Engine Controller) display is
"OFF" (not lit).

2. Let the engine cool by running it for 3-5 minutes with no

load applied.

5. Remove the load from the UVWO terminal strip (Figure 18

on page 48).

3. Place the Off/Manual/Auto Switch (Figure 52) in the "OFF/

RESET" position

DCA-400SSK — GENERATOR SHUTDOWN PROCEDURE