Shutdown Procedure - Engine Controller
(S/N 73002141
~)

To shutdown the generator use the following procedure:

1. Place both the MAIN, GFCI and LOAD circuit breakers

as shown in Figure 45 to the "OFF“ position.

2. Place the

engine speed switch in the “LOW” position

(Figure 73).

Figure 73. Engine Speed Switch (Low)

3. Let the engine cool by running it for 3-5 minutes with no

load applied.

4. Place the

Auto-Off/Reset-Manual switch (Figure 74) to

the “OFF/Reset“ position.

Figure 74. Off/Manual Auto Switch (Off)

5. Verify that the

all status LED on the MPEC display

(Figure 68) are "OFF" (not lit).

6. Remove all loads from the generator.

DCA-70SSJU SERIES — GENERATOR SHUT-DOWN PROCEDURE

Shutdown Procedure - Ignition Switch
(Up to S/N 73002140)

To shutdown the generator use the following procedure:

1. Place both the MAIN, GFCI and LOAD circuit breakers

as shown in Figure 45 to the "OFF“ position.

2. Place the

engine throttle control in the “LOW” position

(Figure 71).

Figure 71. Engine Throttle Control (Low)

3. Let the engine cool by running it for 3-5 minutes with no

load applied.

4. Turn the

Ignition Key Switch (Figure 72) to the “OFF

position.

Figure 72. Engine Ignition Switch (Stop)

5. Remove all loads from the generator.

NEVER stop the engine suddenly except
in an emergency. DO NOT use the

emergency stop switch a as method of
shutting down the generator. This switch is

ONLY to be used in the event of an
emergency.

CAUTION

CAUTION

CAUTION

CAUTION

CAUTION:

Emergency Shutdown Procedure - Engine Controller
(S/N 73002141
~)

1. To shut-down the engine in the event of an emergency,

switch the

MAIN, GFCI and LOAD (Figure 45) circuit

breakers to “OFF” position.

2. Place the

Auto-Off/Reset-Manual switch (Figure 74) to

the “OFF/Reset“ position.

Emergency Shutdown Procedure - Ignition Switch
(Up to S/N 73002140)

1. To shut-down the engine in the event of an emergency,

switch the

MAIN, GFCI and LOAD (Figure 61) circuit

breakers to “OFF” position.

2. Turn the

ignition switch key to the “STOP” position

(Figure 72).