Generator outputs, Generator output voltages, Voltage selector switch – Multiquip DCA70SSIU2 User Manual
Page 26: Voltage selector switch locking button, Generator amperage, Gfci receptacle load capability

PAGE 26 — DCA70SSIU2 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #0 (05/29/09)
GENERATOR OUTPUTS
GENERATOR OUTPUT VOLTAGES
A wide range of voltages are available to supply voltage for
many different applications. Voltages are selected by using
the voltage selector switch (Figure 13). To obtain some of
the voltages as listed in Table 7 (see below) will require a
fi ne adjustment using the voltage regulator (VR) control
knob located on the control panel.
Voltage Selector Switch
The voltage selector switch (Figure 13) is located above
the output terminal panel’s Hard Wire Hook-up Panel. It
has been provided for ease of voltage selection.
Voltage Change-Over Board
Figure 13.
Voltage Selector Switch Locking Button
The voltage selector switch has a locking button to protect
the generator and load from being switched while the
engine is running. To lock the voltage selector switch, press
and hold the red button located at the bottom of the switch.
CAUTION
NEVER change the position of the voltage selector
switch while the engine is running. ALWAYS place
circuit breaker in the OFF position before selecting
voltage.
Voltages Available
Table 7.
Three Phase
(Switchable)
208V
220V
240V
416V
440V
480V
Single Phase
(Switchable)
120V
1127V
139V
240V
254V
277V
Generator Amperage
Table 8 shows the maximum amps the generator can
provide. DO NOT exceed the maximum amps as listed..
GFCI Receptacle Load Capability
The load capability of the GFCI receptacles is directly
related to the voltage being supplied at either the output
terminals or the 2 twist lock auxiliary receptacles.
Tables 9 and 10 show what amount of current is available
at the GFCI receptacles when the output terminals and
twist lock receptacles are in use. Be careful that your load
does not to exceed the available current capability at the
receptacles.
Generator Maximum Amps
Table 8.
Rated Voltage
Maximum Amps
1Ø 120 Volt
155.5 X 2 amps (4 wire)
1Ø 240 Volt
78.8 amps (4 wire)
3Ø 240 Volt
168 amps
3Ø 480 Volt
84 amps
1Ø GFCI Receptacle Load Capacity
Table 9.
KW in Use
Twist Lock (C6369)
Available Load
Current (Amps)
1Ø 240/120V
GFCI Duplex
5-20R 120V
40.4
0
39.2
5 amps/receptacle
38.0
10 amps/receptacle
38.6
15 amps/receptacle
35.6
20 amps/receptacle
3Ø Generator Maximum Amps
Table 10.
KVA in Use
(UVWO Terminals)
Available Load
Current (Amps)
3Ø 240/480V
GFCI Duplex
5-20R 120V
70
0 amps/receptacle
65.8
5 amps/receptacle
61.7
10 amps/receptacle
57.5
15 amps/receptacle
53.4
20 amps/receptacle