Drive control & communication – Lenze SCF Series Drives Modbus Communications User Manual
Page 26
RG-SFMOD 22
Drive Control & Communication
AC Tech
Register
Number
(hexadecimal
representation)
Parameter
1
Parameter Name
Range of Adjustment
Modbus value (decimal value)
Factory Default
92 (5CH)
42
Accel / Decel #2
1 – 36000 (0.1 sec – 3600.0 sec)
200 (20.0 sec)
93 (5DH)
43
Serial Address
1 - 247
1
94 (5EH)
44
Password
000 - 999
225
45
Not Used
46
Not Used
97 (61H)
47
Clear History
01 - Maintain
02 - Clear
01 - Maintain
98 (62H)
48
Program Selection
01 - User Settings
02 - OEM Settings
03 - Reset OEM
04 - Reset 60
05 - Reset 50
04 - Reset 60
99 (63H)
49
Not Used
Diagnostic – Read Only Parameters! (50# - 60#)
100 (64H)
50
FAULT HISTORY
Must Read 4 Words (Read Only)
See Note [5]
101 (65H)
51
SOFTWARE VERSION
Must Read 1 or 4 Words (Read Only)
See Note [6]
102 (66H)
52
BUS VOLTAGE [%]
0-250 (MIN 0% MAX 250%)
Read Only
103 (67H)
53
ACTUAL MOTOR
VOLTAGE [%]
0-250 (MIN 0% MAX 250%)
Read Only
104 (68H)
54
MOTOR LOAD [%]
0-250 (MIN 0% MAX 250%)
Read Only
105 (69H)
55
0-10VDC analog input
[100% = 10VDC]
0-250 (MIN 0% MAX 250%)
Read Only
106 (6AH)
56
4-20mA analog input
[100% = 20mA]
0-250 (MIN 0% MAX 250%)
Read Only
107 (6BH)
57
DIGITAL I/O
SERIAL READ - DIGITAL I/O REPRESENTATION
See Note [7]
108 (6CH)
58
DIGITAL I/O
SERIAL READ - DIGITAL I/O REPRESENTATION
See Note [7]
109 (6DH)
59
ANALOG OUTPUT TB30
[100% = 10VDC]
0-250 (MIN 0% MAX 250%)
Read Only
110 (6EH)
60
ANALOG OUTPUT TB31
[100% = 10VDC]
0-250 (MIN 0% MAX 250%)
Read Only
1
= Drive's programming parameter number