3 reference and links, Reference and links, P1 points – Lenze MCH Series Drives Siemens P1 User Manual
Page 15
RG-MHSP1F
12
P1 Points
Point 92: This point indicates the type of fault on which the drive is currently tripped. This point returns
a value between 0 and 24 which corresponds to one of the following fault conditions:
VALUE
FAULT
VALUE
FAULT
0
NO FAULT
13
CONTROL FAULT
1
OUTPUT FAULT
14
LANGUAGE
2
E-STOP
15
EXTERNAL FAULT
3
HIGH DC BUS VOLTS
16
INTERNAL16
4
HIGH DRIVE TEMPERATURE
17
POWER TRANSIENT
5
THERMAL OVERLOAD
18
S/W ERROR #1
6
OUTPUT FAULT
19
S/W ERROR #2
7
LOW DC BUS VOLTS
20
S/W ERROR #3
8
START ERROR
21
S/W ERROR #4
9
DC BRAKE ERROR
22
S/W ERROR #5
10
FOLLOWER LOSS
23
GENERAL S/W ERROR
11
DB ERROR
24
SERIAL COMMUNICATION LOSS
12
POWER SAG
Point 93: This point indicates whether or not the drive is currently tripped on a fault. This point returns
OK (0) if the drive is not in a fault condition or FAULT (1) if it is.
Point 94: This point is used to clear the current fault through the FLN. Set this point to RESET (1) to clear
the present fault. Once the fault has been cleared, the value of this point will automatically
return to NORMAL (0).
Point 99: This point is not used by the MCH Series P1 drive and is, therefore, not capable of being
commanded. When read, this point will always return a value of 0.
4.3 Reference and Links
MCH Series Variable Frequency Drives visit:
http://www.lenze-actech.com
Siemens Building Technologies visit:
http://www.buildingtechnologies.usa.siemens.com/
The APOGEE Building Automation System visit:
http://www.buildingtechnologies.usa.siemens.com/Products__and__Systems/Building_
automation_and_control/APOGEE_Building_Automation_System/Overview/standard_
protocols.htm