4 technical data, General data and operating conditions, Technical data – Lenze ERBMxxxRxxxW User Manual
Page 35

Technical data
General data and operating conditions
4
EDKRBM001 DE/EN/FR 5.0
35
l
H1_Daten−Abm_BF3_BL
4
Technical data
General data and operating conditions
Conformity and approval
Conformity
CE
2006/95/EC
Low−Voltage Directive
Protection of persons and equipment
Enclosure
EN 60529
IP20
NEMA 250
Protection
against contact
to type 1
Thermal contact
Design
NC contact, 130 °C
Switching
capacity
250 V AC / 0.5 A
Environmental conditions
Climate
Storage
IEC/EN 6072
1−3−1
1K3 (−25 ... +60 °C)
Transport
IEC/EN 6072
1−3−2
2K3 (−25 ... +70 °C)
Operation
IEC/EN 6072
1−3−3
3K3 (−10 ... +55 °C)
Current derating from +45 ... +55 °C:
2.5 %/°C
Site altitude
0 ... 4000 m amsl
1000 ... 4000 m amsl: Current
derating 5 %/1000 m
Vibration
resistance
(9.81 m/s
2
= 1 g)
EN 50178,
IEC 61800−5−
1,
Germanisch
er Loyd,
general
conditions
Acceleration resistant up to 1 g
Mounting conditions
Mounting
location
l
In the control cabinet
l
The mounting location must
comply with the device features
mentioned in the chapter "General
data".
l
Flammable materials or
substances may not be placed in
the vicinity of the brake resistor.
l
The heat generated by the brake
resistor must be dissipated freely.
Mounting
position
Vertically suspended with connecting
cables at the bottom.
Free space
at the top
> 100 mm
at the bottom
> 100 mm
to the sides
> 25 mm