Displays – Lenze E94AYAE SM301 User Manual
Page 19
EDK94AYAE DE/EN/FR/ES/IT 3.0
19
l
M5Lieferumfang−LED_An_Aus_Taktzeit
Displays
Pos.
Colour
State
Description
MS
(Module State)
Green
On
Drive−based safety has initialised without a fault.
Blinking
Drive−based safety has initialised without a fault.
Internal communication to the standard device is not
possible.
Flashing
Drive−based safety is in service status.
For exiting, parameterise the drive−based safety.
Off
Drive−based safety is not initialised.
Acknowledgement is not possible.
EN
(Enable)
Yellow
On
Controller enabled
Off
Non−safe display "STO"
ME
(Module Error)
Red
On
System error
Blinking
Trouble
Flashing
Warning
Off
Error−free operation
AS
(Acknowledge
Stop)
Yellow
On
Request of an acknowledgement for the restart or the
parameter set adoption
Blinking
SS1/STO active
Flashing
SS2/SOS active
Off
No stop function active
BE
(Bus Error)
Red
On
Safety bus error:
l
Communication is not possible.
l
Acknowledgement is possible.
Blinking
Safety bus error: no valid configuration.
Off
Safety bus: error−free operation.
DE
(Drive Error)
Red
On
Drive−based safety is not accepted by the standard
device (see notes in the instructions for the standard
device).
Off
Drive−based safety is correctly recognised by the
standard device.
Blinking: on/off every 0.5 s
Flashing: on/off every 0.1/0.9 s