beautypg.com

Installation – New Buck Corporation GAS STOVE HEATER User Manual

Page 19

background image

4. Check all joints of gas supply

piping system. Apply mixture of
liquid soap and water to gas
joints. Bubbles forming show a
leak.

5. Correct all leaks at once.
6. Reconnect

heater and equipment

shutoff valve to gas supply.
Check reconnected fittings for
leaks.


Test Pressures Equal To or Less
Than 1/2 psi (3.5 kPa)


1. Close equipment shutoff valve

(See Figure 19).

2. Pressurize supply piping system

by either using compressed air or
opening main gas valve located
on or near gas meter.

3. Check all joints from gas meter

to equipment shutoff valve (See
Figure 20). Apply mixture of
liquid soap and water to gas
joints. Bubbles forming show a
leak.

4. Correct all leaks at once.

Pressure Testing Heater Gas
Connections


1. Open equipment shutoff valve (See

Figure 19).

2. Open main gas valve located on or

near gas meter.

3. Make sure control knob of heater is in

the OFF position.

4. Check all joints from equipment

shutoff valve to control valve (See
Figure 20). Apply mixture of liquid
soap and water to gas joints. Bubbles
forming show a leak.

5. Correct all leaks at once.
6. Light

heater

(See

Operating Heater,

pages 17 through 19). Check all other
internal joints for leaks.

7. Turn off heater (See To Turn Off Gas

to Appliance on pages 17 through
19).

Input Minimum Maximum
Rating 22,400 32,000

Type of Gas LP/Propane Natural
Manifold
Pressure 10.0
"wc 3.5"wc
*Min. Inlet 10.5
"wc 4.5"wc
Max. Inlet 13.0
"wc 10.5"wc

*For purpose of input adjustment.

The appliance must be isolated from the gas
supply piping system by closing its equipment
shutoff valve during any pressure testing of the
gas supply piping system at test pressures equal
to or less than ½ psi (3.5 kPa).

INSTALLATION

Continued

We recommend that you install a
sediment trap in supply line. Locate
sediment trap where it is within reach
for cleaning. Install in piping system
between fuel supply and heater. Locate
sediment trap where trapped matter is
not likely to freeze. A sediment trap
traps moisture and contaminants. This
keeps them from going into heater
controls. If sediment trap is not
installed or is installed wrong, heater
may not run properly.

CAUTION:

Avoid damage to

regulator. Hold gas regulator
with wrench when connecting it
to gas piping and/or fittings.

CHECKING GAS
CONNECTIONS

WARNING:

Test all gas piping

and connections for leaks after
installing or servicing. Correct all
leaks at once.

WARNING:

Never use an open

flame to check for a leak. Apply a
mixture of liquid soap and water
to all joints. Bubbles forming
show a leak. Correct all leaks at
once.

Pressure Testing Gas Supply
Piping System

Test Pressures In Excess of 1/2 psi
(3.5 kPa)

1. Disconnect appliance with its

appliance main gas valve (control
valve) and equipment shutoff valve
from gas supply piping system.
Pressures in excess of 1/2 psi will
damage heater regulator.

2. Cap off open end of gas pipe

where equipment shutoff valve
was connected.

3. Pressurize supply piping system by

either using compressed air or
opening main gas valve located on
or near gas meter.

OPEN

CLOSED

EQUIPMENT
SHUTOFF
VALVE

FIGURE 19 - EQUIPMENT SHUTOFF
VALVE

CONTROL VALVE LOCATION

EQUIPMENT
SHUTOFF
VALVE

GAS METER

FIGURE 20 - CHECKING GAS JOINTS

15