Product description – Lenze 3200 C User Manual
Page 20
Product description
Controls and displays
20
Lenze ¯ BA_3241C ¯ 4.0
LED status displays
LED
Interval
Meaning
Color 1 / Color 2
Power
Green
Is ON
constantly
Starting sequence properly completed.
¯
No pending error
¯
IPC switched on
¯
Supply voltage OK
Yellow
Is ON
constantly
The supply voltage has fallen below the minimum value.
Blinking
(2.0 Hz)
Status after switch−on/restart
Green
Yellow
Blinking
(0.5 Hz)
System clock is not synchronised (missing time
information).
Note:
If the IPC is switched off for longer than two weeks, the set
time information is lost.
¯
The next starting sequence generates a logbook entry
(power LED is blinking green).
¯
Set the current time manually via the »WebConfig«
(parameter 91).
Green
Blinking
(5.0 Hz)
Battery pack (ACCU−PACK) or capacitor pack (CAPS−PACK) is
not fully charged.
The length of the dark bar shows the state of charge:
¯
ACCU/CAPS−PACK almost dead: long dark bar
¯
ACCU/CAPS−PACK almost fully charged: short dark bar
Green
Yellow
Blinking
(5.0 Hz)
Error status of the battery pack (ACCU−PACK) or capacitor
pack (CAPS−PACK)
UPS function not available, possible cause:
¯
Connection to ACCU/CAPS−PACK interrupted
¯
ACCU/CAPS−PACK not connected, cable break/short
circuit
Error
Red
Blinking
(5.0 Hz)
Error:
¯
Fatal error (abort)
¯
SD card not available/not inserted correctly
¯
No operating system licence available
Green
Red
Blinking
(5.0 Hz)
Mains switching required
Status 1 ("busy")
Green
Is ON
constantly
Operating status:
¯
IPC running
¯
PLC project running
Blinking
(0.5 Hz)
Starting sequence of the IPC is active
Green
Yellow
Blinking
(0.5 Hz)
User action required:
¯
Load PLC project (PLC was started, project is not running)
¯
Remove USB stick
Status 2
−
−
No response