B.

For 460-v Motors

The motor leads are color coded as follows:

3-SPEED (060 ONLY)

2-SPEED

black = high speed

black = to purple

-

yellow = line

orange = medium speed

purple = to black

blue = low speed

red = line

To change the speed of the blower motor (BM) from low speed to
high speed, removethe red lead from the indoor-fan relay (IFR).
Insulate the red lead to avoid contact with any chassis parts.
Separate the black lead from the purple lead. Connect the black
lead to the IFR. Insulate the purple lead to avoid contact with any
chassis parts.

V.

UNIT CONTROLS

All compressors have the following internal-protection controls.

A.

HIGH-PRESSURE RELIEF VALVE

This valve opens when the pressure differential between the low
and high side becomes excessive.

B.

COMPRESSOR OVERLOAD

This overload interrupts power to the compressor when either the
current or internal temperature become excessive, and automati-
cally resets when the internal temperature drops to a safe level.
This overload may require up to 60 minutes (or longer) to reset;
therefore, if the internal overload is suspected of being open,
disconnect the electrical power to the unit and check the circuit

Fig. 17—Cooling Charging Chart—564A036 Units

C00017

°

OUTDOOR TEMP

° F

° C

115

46

45

7

55

13

65

18

75

24

95

35

105

41

85

29

Fig. 18—Cooling Charging Chart—564A042 Units

C00018

°

OUTDOOR TEMP

° F

° C

115

46

45

7

55

13

65

18

75

24

95

35

105

41

85

29

Fig. 19—Cooling Charging Chart—564A048 Units

C00019

°

OUTDOOR TEMP

° F

° C

115

46

45

7

55

13

65

18

75

24

95

35

105

41

85

29

Fig. 20—Cooling Charging Chart—564A060 Units

C00020

°

OUTDOOR TEMP

° F

° C

115

46

125

52

45

7

55

13

65

18

75

24

95

35

105

41

85

29

—13—