beautypg.com

Bunn VPS User Manual

Page 10

background image

Page 10

FIG. 6 LIMIT THERMOSTAT TERMINALS

SERVICE (cont.)

CONTROL THERMOSTAT (cont.)

LIMIT THERMOSTAT - VPR, VPS

Location:

The limit thermostat is located inside the hood on

the right side of the tank lid.

P2414

FIG. 5 LIMIT THERMOSTAT

P1800

BLK to Tank
Heater

BLU/BLK to Control
Thermostat

10053 073001

2.

Remove the thermostat capillary bulb by firmly
pulling-up on the capillary at the tank lid. This will
disengage the grommet from the tank lid.

3.

Remove the two #8-32 screws securing the con-
trol thermostat to the mounting bracket inside
the hood.

4.

Slide the grommet to the line 4.5" above the bulb
on the new capillary tube.

5.

Insert the capillary bulb through the hole in the
tank lid and press the grommet firmly and evenly
so that the groove in the grommet fits into the
tank lid.

6.

Carefully bend the capillary tube so that the tube
and bulb inside the tank are in the vertical posi-
tion.

NOTE - The capillary tube must be clear of any electri-

cal termination and not kinked.

7.

Using two #8-32 screws secure the control ther-
mostat to the mounting bracket inside the hood.

8.

Refer to Fig. 4 when reconnecting the wires.

9.

Adjust the control thermostat as required

Test Procedures:
1.

Disconnect the brewer from the power source.

2.

Disconnect the blue/black and black wires from
the limit thermostat.

3.

Check for continuity across the limit thermostat
terminals with an ohmmeter.

If continuity is present as described, the limit thermo-

stat is operating properly.

If continuity is not present as described, replace the

limit thermostat.

Removal and Replacement:
1.

Remove all wires from limit thermostat termi-
nals.

2.

Carefully slide the limit thermostat out from
under the retaining clip and remove limit thermo-
stat.

3.

Carefully slide the new limit thermostat into the
retaining clip.

4.

Refer to Fig. 6 when reconnecting the wires.

This manual is related to the following products: