J3 connector – ElmoMC SimplIQ Analog Servo Amplifiers-Flute Installation User Manual
Page 21

Flute Installation Guide
Installation
MAN-FLUIG (Ver. 2.301)
21
3.6.1.4.
J3 Connector
Pin #/
Short Form
Function
Remarks
1
AOK
Amplifier OK
“Amplifier OK” indication output pin. When
the amplifier is at normal operating
conditions, this output is in “active low “ state.
When a failure occurs, this output is changed
to “open” state. Opto isolated, open collector
NPN type, see Figure 1.
•
Maximum voltage = 30 V
•
Maximum current = 8 mA
•
“On” voltage: V OUT(On) < 0.8 V
2
SO1
Status output 1
Status indication output 1. Specification as in
pin J3/1.
3
SO2
Status output 2
Status indication output 2. Specification as in
pin J3/1.
4
SO3
Status output 3
Status indication output 3. Specification as in
pin J3/1.
5
SORET
Status output return
Status output return for AOK, SO1, SO2, SO3.
Isolated from power input return, for details,
see Figure 1.
6
SORET
Status output return
Status output return for AOK, SO1, SO2, SO3.
Isolated from power input return, for details,
see Figure 1.
Table 6: J3 Connector
3.6.2.
Connecting a Non-isolated Flute to an Isolating Power
Transformer
Be sure to ground:
•
DC power common
•
Motor chassis
•
Amplifier heatsink
Do not ground the control common, which is internally connected to the power common.
Grounding the control common will create a ground loop.