beautypg.com

Ventilation air, Warning – New Buck Corporation 32 User Manual

Page 16

background image

VENTILATION AIR

VENTILATION AIR FROM INSIDE BUILDING

This fresh air would come from an adjoining unconfined space. When venting to an adjoining
space, you must provide two permanent openings: one within 12" of the ceiling and one within
12" of the floor on the wall connecting the two spaces. (See Options 1 and 2, Figure 5). You
can also remove door into adjoining room. (See Option 3, Figure 5).

WARNING

REWORK WORKSHEET, ADDING THE SPACE OF THE ADJOINING
UNCONFINED SPACE. THE COMBINED SPACES MUST HAVE ENOUGH FRESH
AIR TO SUPPLY ALL APPLIANCES IN BOTH SPACES.


NOTE:
Each opening shall have a minimum free area of 1 square inch per 1000 BTU’s per
hour of the total input ratings of all gas utilization equipment in the confined space, but not less
than 100 square inches.

Figure 5: Ventilation Air From Inside Building

NOTE: Drill holes on bottom of pedestal base on each corner. Unit must be fastened to floor
with screws.

Page 14