Fuel consumption, Fuel pipe sizing – Briggs & Stratton 40204 User Manual
Page 11
INSTALLATION
11
Fuel Consumption
See Figure 7 for estimated fuel supply requirements at half
and full load for both natural gas and LP vapor.
Fuel Pipe Sizing
Figures 8 and 9 provide the maximum capacity of pipe in
cubic feet of gas per hour for gas pressures of 0.5 psi or less
and a pressure drop of 0.3 in. water column. Specific gravity
of gas is shown.
Listed values compensate for a nominal amount of restriction
from bends, fittings, etc. If an unusual number of fittings,
bends, or other restrictions are used, please refer to federal
and local codes.
Natural Gas*
LP Vapor**
1/2 Load
Full Load
1/2 Load
Full Load
12kW
102
195
41
79
15kW
140
218
66
96
* = Natural Gas is in cubic feet per hour
** = LP Vapor is in cubic feet per hour
Figure 7 — Fuel Supply Requirements
NPT
10ft
15ft
20ft
30ft
40ft
50ft
60ft
70ft
80ft
90ft
100ft
3/4”
346
293
240
192
163
145
132
120
113
106
99
1”
653
549
446
360
307
274
250
230
211
197
187
Natural Gas (sg=0.65)
NPT
10ft
15ft
20ft
30ft
40ft
50ft
60ft
70ft
80ft
90ft
100ft
3/4”
277
192
158
126
107
95
87
79
74
69
65
1”
428
360
293
236
202
180
164
151
139
129
123
Liquid Propane (LP) (sg=1.50)
Figure 8 — NATURAL GAS (NG) Pipe Size - Gas Flow Chart, in cubic feet per hour
Figure 9 — LIQUID PROPANE (LP) GAS Pipe Size - Gas Flow Chart, in cubic feet per hour