Blue Sea Systems 8379 DC Main + 20 Positions, White Toggle User Manual
Installation, Dc power distribution panel, Warning
1. Disconnect all AC and DC power
Disconnect all AC power originating on or off the vessel. This includes
inverters, generators, shore power attachments and any other device
capable of supplying AC power to the ship’s circuits.
Disconnect the main positive DC cable from all batteries to eliminate the
possibility of a short circuit and to disable the inverter while installing the
distribution
panel.
2. Apply Voltage Label
All panel components are sized for 12 or 24 Volt systems. Use the labels
provided to permanently identify the system voltage and its type (DC) as
required by ABYC. Apply the appropriate voltage label to the recessed
area on the front of the panel.
3. Select mounting location and cut opening
If this panel is to serve as your main shore power disconnect circuit
breaker, select a location which is not more then 10 feet from the shore
power inlet or the electrical attachment point of a permanently installed
shore power cord as measured along the conductors of the feed wires. If
it is more then 10 feet additional fuses or circuit breakers must be
installed within 10 feet of the shore power inlet.
Select a mounting location which is protected from water on the panel
front and back and is not in an area where fl ammable vapors from
propane, gas or lead acid batteries accumulate. The circuit breakers
used in marine electrical panels are not ignition protected and may ignite
such
vapors.
Using the panel template provided, make a cutout in the mounting
surface where the distribution panel is to be mounted. Do not yet fasten
the panel to the mounting surface.
4. Select positive feed wire and negative return
Determine the positive feed (red) and negative return (black or yellow)
wire size by calculating the total amperage of the circuits that will be
routed through the panel. Blue Sea Systems’ electrical panels are rated
Marine Electrical Products
DC Power Distribution Panel
PN 8379 / PN 3379 / PN 8382 / PN 3382
Panel Specifi cations
Material:
0.125” 5052-H32 Aluminum Alloy
Primary Finish:
Chemical Treatment per Mil Spec C-5541C
Final Panel Finish: Graphite color 2 part textured Polyurethane
Amperage Rating: All components are sized for 100 Amps of
continuous current
Voltage Rating:
12 or 24 Volt DC*
* Confi gure your panel with the supplied voltage
identifi cation labels.
PN Inches
Millimeters
Overall Dimensions: 8379/3379 14-3/4 x 7-1/2
374.65 x 190.50
8382/3372 14-3/4 x 11-1/4
374.65 x 254.00
Panel Features
8379 / 3379
• One 100 Ampere C-Series DC main circuit breaker
• Twenty circuit breaker positions, Fourteen 15 Ampere branch
circuit
breakers
installed
• DC digital multimeter PN 8248 with 3 position switch for multiple
battery banks and remote shunt
8382 / 3382
• One 100 Ampere C-Series DC main circuit breaker
• Thirty-fi ve circuit breaker positions, Twenty-six 15 Ampere branch
circuit
breakers
installed
• DC digital multimeter PN 8248 with 3 position switch for multiple
battery banks and remote shunt
Page 1 of 3
WARNING
@
It is not possible within the scope of these instructions to fully acquaint
the installer with all the knowledge of electrical systems that may be
necessary to correctly install this product. If the installer is not
knowledgeable in electrical systems we recommend that an electrical
professional be retained to make the installation.
@
If either the panel front or back is to be exposed to water it must be
protected with a waterproof shield.
@
The panels must not be installed in explosive environments such as gas
engine rooms or battery compartments as the circuit breakers are not
ignition
proof.
@
The main positive connection must be disconnected at the battery post to
avoid the possibility of a short circuit during the installation of this
distribution
panel.
@
The shunt must be installed in the negative line to avoid damage to the
meter. Positive voltage applied to digital meter terminals #4 and #5 will
cause damage to the meter not covered by warranty.
@
The vessel’s shore power cord must be disconnected form shoreside
power before installing this electrical panel.
@
If an inverter is installed on the vessel its power leads must be
disconnected at the battery before the panel installation. Be aware that
many inverters have a “sleep mode” in which their voltage potential may
not be detectable with measuring equipment.
@
If an AC Generator is installed aboard it must be stopped and rendered
inoperable before the panel is installed.
@
Verify that no other AC source is connected to the vessels’ wiring before
the panel is installed.
Blue Sea Systems Inc.
Phone (360) 738-8230
425 Sequoia Drive
Fax (360) 734-4195
Bellingham, WA 98226 USA
E-mail [email protected]
www.bluesea.com
at 100 amp total capacity. The positive feed wire must be sized for 3%
voltage drop at the 100 amp panel rating or the maximum amperage
that will be routed through the panel in any particular installation, which
ever is less. It is recommended that the positive feed wire be sized for
the full panel capacity, which, in most cases, will require at least 2 AWG
wire, assuming a 10 foot wire run between the panel and the batteries in
12 volt systems. Refer to the Wire Sizing Chart for other situations. In the
case of panels with two or more columns of breakers, jumpers from
positive bus to positive bus and from negative bus to negative bus
should be the same size as the positive feed and the negative return
wires.
Remember that the length of the circuit is the total of the positive wire
from the power source and the negative wire back to the DC Negative
Bus. Be certain that there is a fuse or circuit breaker of the correct size
protecting the positive feed wire.
5. Install shunt, negative return and positive feed
The DC digital meter shunt must be installed in the negative line of the
circuit whose current is to be measured. Refer to the DC meter
installation and operation manual prior to installing the shunt. Review the
Theory of Operation, Use, Installation Overview, Installing Shunt, Wiring
Diagram and Wire by Wire Instruction sections. Observe all warning
regarding the shunt installation.
Connect a negative return wire from the negative bus on the panel to DC
negative and ultimately the load side of the shunt. Connect a positive
feed wire from the positive bus on the panel to DC positive. Be certain
that there is a fuse or circuit breaker of the correct size protecting the
positive feed wire.
6. Install battery bank voltage monitor wires
The panel is supplied with a digital meter and switch to monitor the
voltage of three separate sources, usually the batteries. Connect a
minimum 16 AWG red wire from each source to be monitored to each of
the corresponding input wires of the switch. There should be a 1 ampere
fuse in each positive wire near each source.