beautypg.com

Application data – Bryant 569F User Manual

Page 27

background image

27

APPLICATION DATA — 569D072-120, 576C090-120, 569F120

OPERATING LIMITS

NOTES:

1. Select air handler at no less than 300 cfm/ton (nominal condens-

ing unit capacity).

2. Total combined draw of the field-supplied liquid line solenoid valve

and air handler fan contactor must not exceed 22 va. If the speci-
fied va must be exceeded, use a remote relay to control the load.

1. LIQUID LINE — For applications with liquid lift greater than

20 ft, use

1

/

2

-in. liquid line where

3

/

8

in. is shown; use

5

/

8

-in.

liquid line where

1

/

2

in. is shown. The maximum liquid lift is

60 ft.

MAXIMUM REFRIGERANT CHARGE

2. REFRIGERANT PIPING — It is recommended that the

refrigerant piping for all commercial split systems include a
liquid line solenoid valve, a liquid line filter drier, and a sight
glass.

For refrigerant lines longer than 75 lineal ft, a liquid line
solenoid valve and a suction accumulator are required.
Refer to the Refrigerant Specialties table.

MINIMUM OUTDOOR-AIR OPERATING

TEMPERATURE

*Unit has one step of unloading.

REFRIGERANT PIPING SIZES

LEGEND

L — Liquid Line

S — Suction Line

NOTES:

1. Pipe sizes are based on a 2

° F loss for liquid and suction lines.

2. Pipe sizes are based on the maximum linear length, shown for

each column, plus a 50% allowance for fittings.

3. Charge units with R-22 in accordance with unit installation

instructions.

REFRIGERANT SPECIALTIES PART NUMBERS

*Bushings required.

Maximum Cooling Outdoor

115 F

Minimum Outdoor Ambient

See Minimum Outdoor-Air
Operating Temperature
table at right.

Minimum Return-Air

Temperature

55 F

Maximum Return-Air

Temperature

95 F

Normal Acceptable Saturation

Suction Temperature Range

25 to 55 F

Maximum Discharge

Temperature

275 F

Minimum Discharge Superheat

60 F

UNIT

SIZE

R-22 (lb)

569D

072

17.3

090

34.2

120

34.2

576C

120

34.2

569F

120

(2) 17.1

UNIT

SIZE

COMPR

CAPACITY

COND

TEMP

(F)

MINIMUM

OUTDOOR TEMP

(F)

Std

With

Motormaster

®

Control

569D

072

100%

90

35

–20

090

100%

90

35

120

100%

90

35

576C

120*

100%

90

35

67%

80

35

569F

120

100%

90

35

UNIT

SIZE

LINEAR LENGTH OF PIPING — FT

0-25

25-50

50-75

75-100

Line Size (in. OD)

L

S

L

S

L

S

L

S

569D

072

3

/

8

1

1

/

8

3

/

8

1

1

/

8

3

/

8

1

1

/

8

3

/

8

1

1

/

8

090

3

/

8

1

1

/

8

1

/

2

1

1

/

8

1

/

2

1

1

/

8

1

/

2

1

1

/

8

120

1

/

2

1

3

/

8

1

/

2

1

3

/

8

1

/

2

1

3

/

8

1

/

2

1

3

/

8

576C 120

1

/

2

1

3

/

8

1

/

2

1

3

/

8

1

/

2

1

3

/

8

1

/

2

1

3

/

8

569F 120 (2)

3

/

8

(2) 1

1

/

8

(2)

3

/

8

(2) 1

1

/

8

(2)

3

/

8

(2) 1

1

/

8

(2)

3

/

8

(2) 1

1

/

8

UNIT

LIQUID LINE

SIZE (in.)

LIQUID LINE

SOLENOID VALVE (LLSV)

LLSV

COIL

SIGHT

GLASS

FILTER

DRIER

SUCTION LINE

ACCUMULATOR

569D072

3

/

8

200RB5T3M

AMG/24V

AMI-1TT3

P502-8304S*

S-7063S*

569D090

3

/

8

200RB5T3M

AMG/24V

AMI-1TT3

P502-8304S*

S-7063S*

1

/

2

200RB5T4M

AMG/24V

AMI-1TT4

P502-8304S

S-7063S*

569D120

1

/

2

200RB6T4M

AMG/24V

AMI-1TT4

P502-8307S*

S-7063

576C120

1

/

2

200RB6T4M

AMG/24V

AMI-1TT4

P502-8307S*

S-7063

3

/

8

200RB5T3M Qty 2

AMG/24V Qty 2

AMI-1TT3 Qty 2

P502-8304S* Qty 2

S-7061 Qty 2

50
TF
Q

0

0

4

-0

1

2

5

6

9D

07
2-
12
0

, 57
6C

12
0

, 5

6

9F
1

2

0

This manual is related to the following products: