Advanced (advanced) – APG LPU-2428 user manual User Manual
Page 26

LPU-2428
Rev. A3, 11/08
26
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Max mA Value (MaxMaVal)
Limits the high end of the mA output.
Min mA Value – 20.00
Default: 20.00
Min mA Trim (Min Trim)
Fine tunes the minimum mA current. For example, if the 4 mA on the
input device is reading 3.95 mA, increasing this parameter will increase
the minimum mA output.
0 – 999
Default: 500
Max mA Trim (Max Trim)
Fine tunes the maximum mA current. For example, if the 20 mA on the
input device is reading 20.15, decreasing this parameter will decrease
the maximum mA output.
0 – 999
Default: 500
Multiplier (Multipli)
Calibrates the sensor for variations in the speed of sound due to
irregular atmospheric conditions.
0 – 1.999
Default: 1.000
Offset (Offset)
Adjusts the zero reference at the sensor face.
-3.00 ft to +3.00 ft
Default: 0.00
Advanced (Advanced)
Temperature Compensation (TempComp)
Compensates for changes in the speed of sound due to temperature
changes. Note: if the internal temperature compensation is used, care
must be taken that the sensor is not exposed to direct sunlight. The