LPU-2428

Rev. A3, 11/08

24

Automation Products Group, Inc.

APG...Providing tailored solutions for measurement applications

Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]

Submersible (Submersi)

Used to directly replace a pressure transducer.

Submersible Range

0.00 – 25.00 ft
Default: 1.00 ft

Depth Distance: this parameter is used to limit the high end of
the analog output so that it will not go above a programmed
value. This setting becomes the output that is selected at the
20 mA distance. It can be used if it is desired for the sensor to
directly replace a pressure transducer.

1.00 – 25.00 ft
Default: 25.00 ft

4-20 Setup (4-20 Set)

In Distance mode, the zero reference is from the face of the sensor. In
Level, Volume, or Flow modes, zero is referenced from the Zero
Distance, Empty Distance, or Zero Flow.

Minimum (Min) mA Setpoint (MinMaSet)

Sets the minimum mA distance, level, volume, or flow.