Troubleshooting guide – L.B. White I-40 Infraconic Spark Ignition User Manual

Page 19

background image

18

READ THIS ENTIRE SECTION BEFORE
BEGINNING TO TROUBLESHOOT PROBLEMS.

The following troubleshooting flow charts provide systematic
procedures for isolating heater problems. The charts are
intended for use by a QUALIFIED GAS HEATER SERVICE
PERSON. DO NOT SERVICE THE HEATER UNLESS YOU HAVE
BEEN PROPERLY TRAINED.

TEST EQUIPMENT REQUIRED

The following pieces of test equipment will be required to
troubleshoot this system with minimal time and effort.

• Digital Multimeter - For measuring voltage.

• Pressure Gauge - (Part No. 20736) For checking inlet

pressures to the heaters.

INITIAL PREPARATION

-- Inspect the heater for damage.
-- Clean the heater as necessary.

Heater Problems

Page

1. Heater does not light . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

2. Heater lights, but will not stay lit . . . . . . . . . . . . . . . . . . .20

3. Heater backflashes gas through air inlet . . . . . . . . . . . .20

Components should be replaced only after each step has
been completed and replacement is suggested in the flow
chart. Refer to the “Servicing” sections as necessary to
obtain information on disassembly and replacement
procedures of the component once the problem is identified
by the flow chart.

OPERATION SEQUENCE:

--

A call for heat occurs from building thermostat.

--

Line voltage is sent from building’s temperature control

to heater’s ON/OFF switch.

--

Switch sends power to ignition control.

--

Ignition control module begins ignition trial sequence

-- Ignition control sends high voltage to igniter

electrode

-- Igniter sparks
-- Gas control solenoid opens

--

Ignition occurs

-- Igniter continues to spark for 10 seconds until

flame proving occurs

-- Ignition spark is shut off
-- Gas control solenoid stays open

--

Ground warms to desired temperature

-- Building thermostat is satisfied
-- Heater shuts down

--

Process is repeated on a call for heat

IGNITION FAILURE SEQUENCE:

--

Ignition control will make three ignition trials

-- Each trial lasts 10 seconds
-- 15 seconds time span between each trial

--

If ignition control does not establish flame sense within

ignition trial:

-- Ignition spark shuts off
-- Gas valve closes

--

After three ignition trials, ignition control will wait for 15
minutes before retrying for ignition.

--

This process will be repeated continually until the

ignition problem is solved.

--

To manually reset the ignition control:

-- Unplug the heater and plug it back in

OR

-- Turn the building temperature control to off and

then back on.

OR

-- Turn ON/OFF switch on heater off and then on.

Troubleshooting Guide

WARNING

Electrical Shock and Burn Hazard

Troubleshooting this system may require operating the
heater with the burner on. Use extreme caution when
working on the heater.

Failure to follow this warning may result in electrical
shock or burns causing severe injury.