High voltage ignition cable igniter, Fig. 13, Fig. 14 – L.B. White I-40 Infraconic Spark Ignition User Manual
Page 16: Fig. 15
15
1. Remove the control box cover.
2. Disconnect the igniion cable from ignition module.
3. Loosen the water tight connector nut. See Fig. 12.
Pull the ignition lead through this connection.
4. Disconnect the high voltage ignition cable from the
ignitor. See Fig. 13.
5. Remove the connector nut from the ignition cable.
This nut will be used on the replacement ignition
cable.
6. Ensure cable is positioned away from the venturi tube
and its boot is covering the ignitor terminal.
FIG. 13
DISCONNECT FROM
IGNITOR LEAD
LOOSEN NUT
DISCONNECT
NITOR LEAD FROM
CONTROL BOX
B
A
C
1
Disconnect the ignition cable from the ignitor. Remove
ignitor mounting screws. See Fig. 14.
Fig. 14
2. Remove the igniter from the heater. Clean the ignitor
rod with steel wool or emery cloth.
3. The rod and its insulating ceramic body must be rigid
within its mounting bracket. If either are capable of
movement, the igniter will not be properly positioned to
the combustion cone. The igniter must then be
replaced.
Adjusting Ignitor Gap
Gap may need to be adjusted if spark is weak or non-existent
after the ignitor has been either cleaned or replaced. Refer to
the following instructions.
a. Ensure the three burner plate nuts are snuggly
tightened. See Fig 14.
b. To properly check gap, insert gapping tool part # 23967
at opening between inner and outer combustion cone
tips. Position the thickest section of tool between ignitor
tip and inner cone. Adjust gap if needed. See Fig. 15,
shown without outer cone.
Fig. 15
c. If necessary, adjust the gap:
-- loosen igniter mounting screws.
-- reposition the igniter until the gap is
within the proper tolerances.
d. Tighten the igniter mounting screws, and remove gauge.
HIGH VOLTAGE IGNITION CABLE
IGNITER
IGNITOR
TERMINAL
DISCONNECT
CABLE FROM
IGNITION
CONTROL
LOOSEN WATER
TIGHT NUT
DISCONNECT CABLE
FROM IGNITOR
TERMINAL
NUTS
IGNITER
IGNITER
SCREWS
IGNITION CABLE
.175
TOOL