Start-up instructions, Shut-down instructions – L.B. White I-34 Infraconic Pilot Ignition User Manual
Page 11
11
Follow these start-up instruction steps for initial start-up
before building repopulation. For normal start-up, simply
adjust the thermostat on the building’s environment
controller above room temperature.
1.
Open all gas supply valves to the heater(s) and
check for gas leaks at all connections using
approved lead detectors.
2.
Energize the solenoid of the zone control panel to
allow full 5 PSIG flow to the heater.
3.
Fully depress the pilot button on the pilot safety
control valve while applying flame to the main
burner cone point. On initial start-up leave the
main burner on for several minutes to bleed
residual air from the system.
4.
De-energize the solenoid of the zone control panel.
The pilot flame should light and remain lit upon
completion of transition from full output to pilot.
Note:
It is normal to have flame “pop” out of the
air inlet of the heater when cycling from
main burner mode to pilot mode.
5.
Set the thermostat controlling the heater(s) to the
desired temperature.
FIG. 7
Start-Up Instructions
PILOT BUTTON
To reduce temperature, adjust the building’s environmental
control system to its minimum setting.
To shut down the heaters for cleaning, maintenance, or
service:
1.
Shut off all gas supply valves to the heaters.
2.
Allow heaters to burn off fuel gas remaining in the
gas supply line.
3.
Set building environment control to minimum
setting.
Shut-Down Instructions
WARNING
Fire or Explosion Hazard
■
Do not force the gas control button.
■
Use only your hand to depress the gas control button.
Never use any tools.
■
If the button will not depress by normal hand
pressure, the control should be replaced by a
qualified service person.
■
Force or attempted repair may result in fire or
explosion, causing property damage, livestock loss,
severe injury or death.