Bryant 683B User Manual
Page 26
TABLE 17—702B/602B COOLING & HEATING DRY COIL ICM AIRFLOW
LARGE CABINET
UNIT
SIZE
CFM ADJUST
PIN SELECT
LO PIN
NOM PIN
HI PIN
EXTERNAL STATIC
PRESSURE RANGE
0.1–1.0
0.1–1.0
0.1–1.0
042
COOLING †
1100
1225
1410
COOLING
DEHUMIDIFY
980
980
1125
HEAT PUMP
COMFORT (602B Only)
990
1100
1265
048
COOLING †
1260
1400
1610
COOLING
DEHUMIDIFY
1120
1120
1290
HEAT PUMP
COMFORT (602B Only)
1135
1260
1450
060
COOLING †
1575
1750
2010
COOLING
DEHUMIDIFY
1400
1400
1610
HEAT PUMP
COMFORT (602B Only)
1415
1575
1810
†
Heat Pump Efficiency
and
Cooling
pin selections deliver equal airflow
TABLE 18—MINIMUM AIRFLOW FOR RELIABLE ELECTRIC HEATER OPERATION (CFM)
UNIT
SIZE
024
030
036
042
048
060
602B
750
1025
1250
1285
1710
1800
702B
750
750
1250
1205
1500
1800
TABLE 19—ELECTRIC HEAT PRESSURE DROP TABLE (IN. WG)
SMALL CABINET
STATIC
CFM
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
5 kW
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.02
0.04
0.06
0.07
7.5 kW
0.00
0.00
0.00
0.00
0.00
0.00
0.02
0.03
0.05
0.07
0.08
0.09
10 kW
0.00
0.00
0.00
0.00
0.00
0.02
0.04
0.06
0.07
0.09
0.10
0.11
15 kW
0.00
0.00
0.00
0.02
0.04
0.06
0.08
0.10
0.12
0.14
0.16
0.18
20 kW
0.00
0.00
0.02
0.04
0.06
0.08
0.09
0.11
0.13
0.15
0.17
0.19
TABLE 20— ELECTRIC HEAT PRESSURE DROP TABLE (IN. WG)
LARGE CABINET
STATIC
CFM
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
5 kW
0.00
0.00
0.00
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
7.5 kW
0.00
0.00
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
10 kW
0.00
0.00
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
15 kW
0.00
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.14
0.15
20 kW
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.14
0.15
0.16
—26—