Bryant 683B User Manual
Page 19
TABLE 8—702B WITH ICM FIOP ELECTRICAL DATA
UNIT
SIZE 702B
V-PH-HZ
VOLTAGE
RANGE
COMPRESSOR
OUTDOOR
FAN
MOTOR
INDOOR
FAN
MOTOR
ELECTRIC
HEAT
SINGLE POINT
POWER SUPPLY
MIN MAX
RLA
LRA
FLA
FLA
Nominal kW*
FLA
MCA
MAX FUSE
OR CKT. BKR.
MOCP
024
208/230–1–60 187
253
13.5
61.0
0.9
4.3
-/-
3.8/5.0
5.4/7.2
7.5/10.0
-/-
18.1/20.8
25.9/30.0
36.1/41.7
22.1/22.1
27.9/31.4
37.8/42.9
50.5/57.5
30/30
30/35
40/50
60/60
–
–
–
–
030
208/230–1–60 187
253
14.7
73.0
0.9
4.3
-/-
3.8/5.0
5.4/7.2
7.5/10.0
-/-
18.1/20.8
25.9/30.0
36.1/41.7
23.5/23.5
27.9/31.4
37.8/42.9
50.5/57.5
30/30
30/35
40/50
60/60
–
–
–
–
036
208/230–1–60 187
253
15.4
83.0
0.9
6.8
-/-
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
-/-
18.1/20.8
25.9/30.0
36.1/41.7
54.2/62.5
27.0/27.0
31.1/34.5
40.9/46.0
53.6/60.6
76.2/86.6
35/35
35/40
50/50
60/–
–
–
–
–
–/70
80/90
042
208/230–1–60 187
253
18.6
105.0
0.9
6.8
-/-
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
15.0/20.0
-/-
18.1/20.8
25.9/30.0
36.1/41.7
54.2/62.5
72.2/83.3
31.0/31.0
31.1/34.5
40.9/46.0
53.6/60.6
76.2/86.6
98.8/112.7
40/10
40/40
50/50
60/–
–
–
–
–
–
–/70
90/90
100/125
048
208/230–1–60 187
253
20.5
109.0
1.6
6.8
-/-
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
15.0/20.0
-/-
18.1/20.8
25.9/30.0
36.1/41.7
54.2/62.5
72.2/83.3
34.0/34.0
34.0/34.5
40.9/46.0
53.6/60.6
76.2/86.6
98.8/112.7
40/40
40/40
50/50
60/-
–
–
–
–
–
–/70
90/90
100/125
060
208/230–1–60 187
253
27.6
158.0
1.6
9.1
-/-
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
15.0/20.0
-/-
18.1/20.8
25.9/30.0
36.1/41.7
54.2/62.5
72.2/83.3
45.2/45.2
45.2/45.2
43.8/48.9
56.5/63.5
79.1/89.5
101.6/115.5
60/60
60/60
50/50
60/-
–
–
–
–
–
–/70
90/90
110/125
* Heater capacity (kW) based on heater voltage of 208-v & 240-v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. Refer
to
Multiplication Factors
Table 23.